FOXBORO

Foxboro DNBI Control Module

Electronics Housing and Housing Covers

Housing has two compartments to separate the

electronics from the field connections. The housing

and covers are made from low copper (0.6%

maximum) die-cast aluminum alloy with an epoxy

finish, or from 316 ss. Buna-N O-ring seals are used

to seal the threaded housing covers, housing neck,

and terminal block.

Electrical Terminations

Field wires enter through 1/2 NPT, PG 13.5. or M20

threaded entrances, as specified, on either side of

the electronics housing. Wires terminate under

screw terminals and washers on terminal block in

the field terminal compartment as shown in Figure .

Unused threaded field wire entrance is plugged to

insure moisture and RFI/EMI protection.

Three- or Four-Wire Connections

Transmitter is supplied with a 4-wire terminal block,

with the two negative terminals connected internally.

This means that the transmitter can be wired with

either three wires for wiring economy, or four wires

for maximum accuracy. For relatively short wiring

runs having low resistance, 3-wire connections can

be used to minimize wiring costs. However, a voltage

drop in the common lead carrying the power supply

current will cause an error in the 1 to 5 V dc signal.

For wiring runs with high resistance due to long

lengths (or other reasons), or for maximum

accuracy, a 4-wire connection may be used to

provide input-output isolation. With 4-wire

configurations, voltage drop in the power supply loop

will have minimal effect on measurement.

Configuration and Calibration Data, and

Electronic Upgradeability

All factory characterization data, and user

configuration and calibration data are stored in the

sensor. This means that the electronics module may

be replaced, with one of like type, without the need

for reconfiguration or recalibration. Although module

replacement can affect accuracy up to 0.20% of

span, this error can be removed by an mA trim

without application of pressure.

Changing module types (from one protocol to

another) may require reconfiguration and

recalibration, as well as a different terminal block,

but all factory characterization data is retained.

Optional External Zero Adjustment

An external pushbutton (Figure 3) mechanism is

isolated from the electronics compartment and

magnetically activates an internal reed switch

through the housing. This eliminates a potential leak

path for moisture or contaminants to get into the

electronics compartment. This zero adjustment can

be disabled by a configuration selection.

Optional Transmitter Mounting Bracket Sets

Numerous mounting bracket set options are offered

to accommodate almost any mounting configuration

required. See “DIMENSIONS – NOMINAL” on

page 36.

PRT PSA300R-81
PTM PSMU-350-3
PULS SLA8.100
QSI QTERM-K65
R-2528Z R-2528Z
RADISYS EPC-16
RADISYS EPC-5 W/ EXM-13
RADISYS SBC486DX66
RAMIX PMC008A 700502
RAMIX PMC237C-008EMI
RAMIX PMC661J
RAMIX PMC676TX
RAYCHEM EMDR

Optional Custom Configuration (Option -C2)

For the transmitter to be custom configured by the

factory, the user must fill out a data form. If this

option is not selected, a standard default

configuration will be provided; for example:

Features

The key features of the Compact FBM242 module are listed below:

 16 discrete outputs

 Supports discrete output signals for the following voltages

– 15 to 60 VDC

– 120 VAC/125 VDC

– 240 VAC

 Each output is galvanically isolated; group-isolated when used with external excitation.

 Compact and rugged, suitable for enclosures in Class G3 (harsh) environments

 Executes discrete I/O or ladder logic programs, configurable with the following options:

Input Filter Time, Fail Safe Configuration, Fail Safe Fallback, Continuous or Instantaneous Outputs

 Various terminal assemblies (TAs) that include the following

– Current limiting devices

– Fuses

– Relay outputs with external power supply, fuses and distribution

– Solid-state outputs

– Redundant power distribution

The FCP280 also supports the following functions:

– Setting and reading FCP280 beacons via panel pushbuttons

– Function Block Alarm Enhancement:

Re-alarm on alarm priority change

Re-alarm on configurable time-delayed dead zones and suppress alarms based on time

– Optional UTC external time synchronisation

– Improved controller performance

– The optional self-hosted mode allows the FCP280 to boot up and run,

executing configured control schemes using checkpoint files stored in flash memory.