Foxboro FCM100E Field Communication Module

Electronics Housing and Housing Covers

Housing has two compartments to separate the

electronics from the field connections. The housing

and covers are made from low copper (0.6%

maximum) die-cast aluminum alloy with an epoxy

finish, or from 316 ss. Buna-N O-ring seals are used

to seal the threaded housing covers, housing neck,

and terminal block.

Electrical Terminations

Field wires enter through 1/2 NPT, PG 13.5. or M20

threaded entrances, as specified, on either side of

the electronics housing. Wires terminate under

screw terminals and washers on terminal block in

the field terminal compartment as shown in Figure .

Unused threaded field wire entrance is plugged to

insure moisture and RFI/EMI protection.

Three- or Four-Wire Connections

Transmitter is supplied with a 4-wire terminal block,

with the two negative terminals connected internally.

This means that the transmitter can be wired with

either three wires for wiring economy, or four wires

for maximum accuracy. For relatively short wiring

runs having low resistance, 3-wire connections can

be used to minimize wiring costs. However, a voltage

drop in the common lead carrying the power supply

current will cause an error in the 1 to 5 V dc signal.

For wiring runs with high resistance due to long

lengths (or other reasons), or for maximum

accuracy, a 4-wire connection may be used to

provide input-output isolation. With 4-wire

configurations, voltage drop in the power supply loop

will have minimal effect on measurement.

Configuration and Calibration Data, and

Electronic Upgradeability

All factory characterization data, and user

configuration and calibration data are stored in the

sensor. This means that the electronics module may

be replaced, with one of like type, without the need

for reconfiguration or recalibration. Although module

replacement can affect accuracy up to 0.20% of

span, this error can be removed by an mA trim

without application of pressure.

Changing module types (from one protocol to

another) may require reconfiguration and

recalibration, as well as a different terminal block,

but all factory characterization data is retained.

Optional External Zero Adjustment

An external pushbutton (Figure 3) mechanism is

isolated from the electronics compartment and

magnetically activates an internal reed switch

through the housing. This eliminates a potential leak

path for moisture or contaminants to get into the

electronics compartment. This zero adjustment can

be disabled by a configuration selection.

Optional Transmitter Mounting Bracket Sets

Numerous mounting bracket set options are offered

to accommodate almost any mounting configuration

required. See “DIMENSIONS – NOMINAL” on

page 36.

Optional Custom Configuration (Option -C2)

For the transmitter to be custom configured by the

factory, the user must fill out a data form. If this

option is not selected, a standard default

configuration will be provided; for example: