FOXBORO

Foxboro P0500JX Peripheral Cable

Adjustable Damping

Transmitter response time is normally 0.75 s, or the

electronically adjustable setting of 0 (none), 2. 4. or

8 seconds, whichever is greater, for a 90% recovery

from an 80% input step as defined in ANSI/ISA

S51.1. (For 63.2% recovery, 0.50 s with sensors B to

F, and 0.60 s for sensor A.)

Switching and Indirect Lightning Transients

Transmitter withstands transient surges to 2000 V

common mode or 1000 V normal mode without

permanent damage. Output shift is less than 1.0%.

(Per ANSI/IEEE C62.41-1980 and IEC Std. 61000-4-5.)

European Union Directives

 Complies with Electromagnetic Compatibility

Requirements of European EMC Directive

2004/108/EC by conforming to the following EN

and IEC Standards: EN 61326-1. and

IEC 61000-4-2 through 61000-4-6.

 Complies with NAMUR NE 21 Interference

Immunity Requirement, and NAMUR NE 43

overrange and underrange annunciations.

 Conforms to Applicable European Union

Directives (“CE” Logo marked on product).

RFI Effect

Output error is less than 0.1% of calibrated span for

frequencies from 27 to 1000 MHz and field intensity

of 30 V/m when transmitter is properly installed,

shielded cable in conduit, grounding, and housing

covers in place. (Per IEC Std. 61000-4-3.)

Electronics Module

Printed wiring assemblies are conformally coated for

moisture and dust protection.

Minimum Allowable Absolute Pressure vs.

Transmitter Temperature

WITH SILICONE FILL FLUID

Full vacuum: up to 121°C (250°F)

WITH INERT FILL FLUID (see Figure 1)

Figure 1. Minimum Allowable

Absolute Pressure vs. Transmitter Temperature,

Inert FC-43. 2.6 cSt at 25°C (77°F)

TEMPERATURE, ˚C-30

ABSOLUTE PRESSURE, mmHg

Electronics Housing and Housing Covers

Housing has two compartments to separate the

electronics from the field connections. The housing

and covers are made from low copper (0.6%

maximum) die-cast aluminum alloy with an epoxy

finish, or from 316 ss. Buna-N O-ring seals are used

to seal the threaded housing covers, housing neck,

and terminal block.

Electrical Terminations

Field wires enter through 1/2 NPT, PG 13.5. or M20

threaded entrances, as specified, on either side of

the electronics housing. Wires terminate under

screw terminals and washers on terminal block in

the field terminal compartment as shown in Figure .

Unused threaded field wire entrance is plugged to

insure moisture and RFI/EMI protection.

Three- or Four-Wire Connections

Transmitter is supplied with a 4-wire terminal block,

with the two negative terminals connected internally.

This means that the transmitter can be wired with

either three wires for wiring economy, or four wires

for maximum accuracy. For relatively short wiring

runs having low resistance, 3-wire connections can

be used to minimize wiring costs. However, a voltage

drop in the common lead carrying the power supply

current will cause an error in the 1 to 5 V dc signal.

For wiring runs with high resistance due to long

lengths (or other reasons), or for maximum

accuracy, a 4-wire connection may be used to

provide input-output isolation. With 4-wire

configurations, voltage drop in the power supply loop

will have minimal effect on measurement.