Foxboro FBM09 Input Interface Module
Adjustable Damping
Transmitter response time is normally 0.75 s, or the
electronically adjustable setting of 0 (none), 2. 4. or
8 seconds, whichever is greater, for a 90% recovery
from an 80% input step as defined in ANSI/ISA
S51.1. (For 63.2% recovery, 0.50 s with sensors B to
F, and 0.60 s for sensor A.)
Switching and Indirect Lightning Transients
Transmitter withstands transient surges to 2000 V
common mode or 1000 V normal mode without
permanent damage. Output shift is less than 1.0%.
(Per ANSI/IEEE C62.41-1980 and IEC Std. 61000-4-5.)
European Union Directives
Complies with Electromagnetic Compatibility
Requirements of European EMC Directive
2004/108/EC by conforming to the following EN
and IEC Standards: EN 61326-1. and
IEC 61000-4-2 through 61000-4-6.
Complies with NAMUR NE 21 Interference
Immunity Requirement, and NAMUR NE 43
overrange and underrange annunciations.
Conforms to Applicable European Union
Directives (“CE” Logo marked on product).
RFI Effect
| PIONEER MAGNETICS | PM3326B-6-1-2-E 80026-529-01 |
| PIONEER MAGNETICS | PM3328B-6-1-3-E |
| PIONEER MAGNETICS | PM3328BP-6 |
| PIONEER MAGNETICS | PM3398B-6-1-3-E |
| PIONEER MAGNETICS | PM3398B-6-1-3-E 80026-172-24 |
| PIONEER MAGNETICS | PM3398B-6P-1-3P-E 80026-172-23 |
| PIONEER MAGNETICS | PM3398B-6P-1-3P-E |
| PIONEER MAGNETICS | PM3398BP-6-1-3-E |
| POLYSPED | PRD2-200 |
| P-OPEN | P-OPEN-P4-150/PAC-OP150/P4 |
| POSITRONIC | PCIH38F300A1 |
| POTTER & BRUMFIELD | SDAS-01-7Y2S1024 |
| POTTER&BRUMFIELD | SDAS-01-7Y2S1024 |
| POWEC | PMP10.48 SIC |
| POWERBOX | PU200-31C |
| POWEREX | PD411811 |
Output error is less than 0.1% of calibrated span for
frequencies from 27 to 1000 MHz and field intensity
of 30 V/m when transmitter is properly installed,
shielded cable in conduit, grounding, and housing
covers in place. (Per IEC Std. 61000-4-3.)
Electronics Module
Printed wiring assemblies are conformally coated for
moisture and dust protection.
Minimum Allowable Absolute Pressure vs.
Transmitter Temperature
WITH SILICONE FILL FLUID
Full vacuum: up to 121°C (250°F)
WITH INERT FILL FLUID (see Figure 1)
Figure 1. Minimum Allowable
Absolute Pressure vs. Transmitter Temperature,
Inert FC-43. 2.6 cSt at 25°C (77°F)
TEMPERATURE, ˚C-30
ABSOLUTE PRESSURE, mmHg
Electronics Housing and Housing Covers
Housing has two compartments to separate the
electronics from the field connections. The housing
and covers are made from low copper (0.6%
maximum) die-cast aluminum alloy with an epoxy
finish, or from 316 ss. Buna-N O-ring seals are used
to seal the threaded housing covers, housing neck,
and terminal block.
Electrical Terminations
Field wires enter through 1/2 NPT, PG 13.5. or M20
threaded entrances, as specified, on either side of
the electronics housing. Wires terminate under
screw terminals and washers on terminal block in
the field terminal compartment as shown in Figure .
Unused threaded field wire entrance is plugged to
insure moisture and RFI/EMI protection.
Three- or Four-Wire Connections
Transmitter is supplied with a 4-wire terminal block,
with the two negative terminals connected internally.
This means that the transmitter can be wired with
either three wires for wiring economy, or four wires
for maximum accuracy. For relatively short wiring
runs having low resistance, 3-wire connections can
be used to minimize wiring costs. However, a voltage
drop in the common lead carrying the power supply
current will cause an error in the 1 to 5 V dc signal.
For wiring runs with high resistance due to long
lengths (or other reasons), or for maximum
accuracy, a 4-wire connection may be used to
provide input-output isolation. With 4-wire
configurations, voltage drop in the power supply loop
will have minimal effect on measurement.