Shinkawa MODEL VM-5K DUAL VIBRATION MONITOR

Shinkawa MODEL VM-5K DUAL VIBRATION MONITOR

ALARM SET VALUE DANGER1 :

ALERT1 :

DANGER2 :

ALERT2 :

Unless specified otherwise, preset to :

DANGER : 100% of monitor range

ALERT : 90% of monitor range

ALARM INDICATOR DANGER : (red LED)

ALERT : (yellow LED)

ABNOR. ALARM

INDICATOR

OK : (green LED)

BYPASS INDICATOR BYPASS : (red LED)

TRANSDUCER INPUT VK-202A,VK-202P,FK-202F,VK-302P,FK-302F,VC Series

Number of input points  :  2 points

SEQUENCE SET

VALUE

(to increase alarm set

value during operation

of the sequence circuit)

:   ×1.0 to 10.0 (×0.1 step)

Preset to ×1.0 unless specified otherwise.

CAUTION : Set the alarm set value so that its designated

multiple is within 110% of the measurement

range during operation of the sequence circuit.

If set to more than 110%, alarm may not be

output.

INPUT IMPEDANCE Approx. 50k

EXTERNAL CONTACT

INPUT

(FROM REAR PANEL)

Contact type : Dry contact

Contact for external reset

Contact for sequence

BAR GRAPH METER Recorder output conversion accuracy  ± 2.5% of F.S.

DIGITAL METER Recorder output conversion accuracy  ± 1.0% of F.S.

RECORDER OUTPUT

CONVERSION

ACCURACY

GE IS230PCAAH1B
moog G123-817-006
IFM VTV122
GE IS220PAOCH1BE
HONEYWELL CC-PUIO31
GE IS220PDOAH1B-E
GE IS220YDIAS1A/RM
GE IS220YDOASIA/RM
ABB CB801
ABB AI625
BENTLY 3500/42M
BENTLY 3500/40M
BENTLY 3500/33
GE IS230TSVCH1A
GE IS220PTCCH1A
GE IS220PPRAS1B
Meggitt MPC4 200-510-074-114
Pioneer Magnetics PM2722-1 24F33-0-4-R-S
ABB DSPC172H 57310001-MP
Metrix 5485C‑007‑046
ABB REF615Z HCFZAEADABCZDAA11G
Hirschmann OZDProfi12MG12 943727‑321

± 0.5% of F.S. at 100Hz at 25°C (77°F REF.)

± 2.0% of F.S. at 100Hz at 0 to 65°C (32 to 149°F REF.) SUPPRESSION

FUNCTION SET VALUE

:   0.0 to 10.0 % of monitor range (0.1 % step)

Preset to 2.0 % unless specified otherwise.

CAUTION : When the measurement value is not more than

suppression function set value, indication and

recorder output value shall be as 0 %.

RECORDER OUTPUT

(FROM REAR PANEL)

Voltage or current output proportional to monitor range

1 to 5VDC (output impedance : 250)

4 to 20mADC (max. load resistance : 500)

0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*

(output impedance : 100) (*option)

Number of output points  :  2 points

Standard Specifications

ALARM SET POINT 4 points (DANGER1.ALERT1.DANGER2.ALERT2) MONITOR OUTPUT

(FROM FRONT, REAR

PANEL)

Input signal is output via a buffer amplifier.

Signal level : -0.8 to -22VDC(VK), 0 to 5VDC(VC)

Output impedance : 100 (load resistance 50k or more)

ALARM SET RANGE 0 to 110% of monitor range

ALARM SET

ACCURACY

± 1.0% of F.S. or less

TEMPERATURE

RANGE

Operating temperature : 0 to 65°C (32 to 149°F REF.)

Storage temperature : -30 to +85°C (-22 to +185°F REF.)

Relative humidity : 20 to 95% (noncondensing)

ALARM SET

REPEATABILITY

± 0.1% of F.S. or less

ALARM OUTPUT 5 points (DANGER1.ALERT1.ALERT2.DANGER2.OK) or

6 points (DANGER1.ALERT1.ALERT2.DANGER2.OK1.OK2)

MATERIAL AND FINISH Face plate : Aluminum Munsell N-4.0 (equiv.)

MASS

Monitor : max.0.7kg (max.1.6lb REF.)

(including single unit instrument rack : max.2.5kg (max.5.5lb REF.))

MEASURED

VIBRATION VALUE

LCD digital meter with 5 digits (7 segments, with back light)

LCD bar graph meter (40 segments, with back light)

* Measurement value and alarm set value are indicated on

the digital meter and bar graph meter simultaneously.