Shinkawa MODEL VM-5K DUAL VIBRATION MONITOR
Shinkawa MODEL VM-5K DUAL VIBRATION MONITOR
ALARM SET VALUE DANGER1 :
ALERT1 :
DANGER2 :
ALERT2 :
Unless specified otherwise, preset to :
DANGER : 100% of monitor range
ALERT : 90% of monitor range
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR. ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCER INPUT VK-202A,VK-202P,FK-202F,VK-302P,FK-302F,VC Series
Number of input points : 2 points
SEQUENCE SET
VALUE
(to increase alarm set
value during operation
of the sequence circuit)
: ×1.0 to 10.0 (×0.1 step)
Preset to ×1.0 unless specified otherwise.
CAUTION : Set the alarm set value so that its designated
multiple is within 110% of the measurement
range during operation of the sequence circuit.
If set to more than 110%, alarm may not be
output.
INPUT IMPEDANCE Approx. 50k
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type : Dry contact
Contact for external reset
Contact for sequence
BAR GRAPH METER Recorder output conversion accuracy ± 2.5% of F.S.
DIGITAL METER Recorder output conversion accuracy ± 1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
| GE | IS230PCAAH1B |
| moog | G123-817-006 |
| IFM | VTV122 |
| GE | IS220PAOCH1BE |
| HONEYWELL | CC-PUIO31 |
| GE | IS220PDOAH1B-E |
| GE | IS220YDIAS1A/RM |
| GE | IS220YDOASIA/RM |
| ABB | CB801 |
| ABB | AI625 |
| BENTLY | 3500/42M |
| BENTLY | 3500/40M |
| BENTLY | 3500/33 |
| GE | IS230TSVCH1A |
| GE | IS220PTCCH1A |
| GE | IS220PPRAS1B |
| Meggitt | MPC4 200-510-074-114 |
| Pioneer Magnetics | PM2722-1 24F33-0-4-R-S |
| ABB | DSPC172H 57310001-MP |
| Metrix | 5485C‑007‑046 |
| ABB | REF615Z HCFZAEADABCZDAA11G |
| Hirschmann | OZDProfi12MG12 943727‑321 |
± 0.5% of F.S. at 100Hz at 25°C (77°F REF.)
± 2.0% of F.S. at 100Hz at 0 to 65°C (32 to 149°F REF.) SUPPRESSION
FUNCTION SET VALUE
: 0.0 to 10.0 % of monitor range (0.1 % step)
Preset to 2.0 % unless specified otherwise.
CAUTION : When the measurement value is not more than
suppression function set value, indication and
recorder output value shall be as 0 %.
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250)
4 to 20mADC (max. load resistance : 500)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100) (*option)
Number of output points : 2 points
Standard Specifications
ALARM SET POINT 4 points (DANGER1.ALERT1.DANGER2.ALERT2) MONITOR OUTPUT
(FROM FRONT, REAR
PANEL)
Input signal is output via a buffer amplifier.
Signal level : -0.8 to -22VDC(VK), 0 to 5VDC(VC)
Output impedance : 100 (load resistance 50k or more)
ALARM SET RANGE 0 to 110% of monitor range
ALARM SET
ACCURACY
± 1.0% of F.S. or less
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (32 to 149°F REF.)
Storage temperature : -30 to +85°C (-22 to +185°F REF.)
Relative humidity : 20 to 95% (noncondensing)
ALARM SET
REPEATABILITY
± 0.1% of F.S. or less
ALARM OUTPUT 5 points (DANGER1.ALERT1.ALERT2.DANGER2.OK) or
6 points (DANGER1.ALERT1.ALERT2.DANGER2.OK1.OK2)
MATERIAL AND FINISH Face plate : Aluminum Munsell N-4.0 (equiv.)
MASS
Monitor : max.0.7kg (max.1.6lb REF.)
(including single unit instrument rack : max.2.5kg (max.5.5lb REF.))
MEASURED
VIBRATION VALUE
LCD digital meter with 5 digits (7 segments, with back light)
LCD bar graph meter (40 segments, with back light)
* Measurement value and alarm set value are indicated on
the digital meter and bar graph meter simultaneously.