GE MVAA12 Auxiliary Relay
MVAA
Auxiliary Relay
Key Benefits
• Compact design
The MVAA is a low burden auxiliary relay for schemes demanding several contacts for
event recording, alarm initiation, contact logic arrangements, etc.
The relay can be supplied fitted with normal duty contacts and/or with heavy duty
blow-out contacts.
MVAA relays are voltage-operated attracted armature units of compact design, featuring
positive action and a high degree of mechanical stability. Voltage is applied to the relay
coils via an internal diode bridge which enables relays to be energised from AC or DC
power supplies.
Typical applications are for general contact multiplication, interlocking and customisation
to suit the substation.
Models
There are five versions of the MVAA relay, each with a different type of contact reset
mechanism:
MVAA 11
Single element relay with self reset contacts (Double element version is
type MVAA 21)
MVAA 13 Single element relay with hand reset contacts (Double element version is
type MVAA 23)
MVAA 14
Single element relay with electrical reset contacts
Contacts
Contacts are made from a silver/copper alloy, shaped and
positioned to ensure very reliable, low resistance operations.
Normal duty make, break and changeover contacts and heavy duty
magnetic blow-out contacts are available in various combinations
(see tables 1. 2 and 3).
Heavy duty magnetic blow-out contacts are recommended for
breaking heavy or highly inductive DC loads. When these are fitted,
the number of contacts available may be reduced (see table 3).
Breaking capacity curves for these contacts are shown in figure 1
on next page.
| GE | 04240FD11234A V2.2 |
| GE | 0880001-01 |
| GE | 104X905BA603 |
| GE | 12A0-0103-A3 |
| GE | 12HFA51A42H |
| GE | 12HGA11J52 |
| GE | 136C2511-1 |
| GE | 151X1233DD01SA02-B1305103 |
| GE | 201CI-1 |
| GE | 208D9845P0008 |
| GE | 239 |
| GE | 2400-21004 2010-3101-0442 |
| GE | 269 PLUS-D/O-100P-125V |
| GE | 269PLUS-D/O-261-100P-120 |
| GE | 336A4940CTP1/SYS000156 |
Operation Indicators
Each relay element is supplied with an optional hand reset
operation indicator.
The indicator consists of a mask, which on operation drops to
expose a broad red strip positioned diagonally on a rectangular
white background
Technical Data
VOLTAGE RATING (V)
24/27
30/34
48/54
OPERATING VOLTAGE RANGE (V)
110/125
220/250
• Frequency: 50/60 Hz
• Withstand rating: The standard relay will withstand 120% of its
maximum voltage rating continuously. High speed variants with
time (where the 10th character of the model number is C or Q)
are short time rated. These must be energised for a maximum of
2 minutes or employ a break contact, wired externally, to cut off
the auxiliary supply after operation
• Burdens: 3 W per element at all rated voltages
• Operating times: The operating times are typically 12-25 ms
depending on the number of contacts and relay type