GE MVAA11 MVAA11R1BA0797A Single-element self-resetting auxiliary relay

MVAA

Auxiliary Relay

Key Benefits

• Compact design

The MVAA is a low burden auxiliary relay for schemes demanding several contacts for

event recording, alarm initiation, contact logic arrangements, etc.

The relay can be supplied fitted with normal duty contacts and/or with heavy duty

blow-out contacts.

MVAA relays are voltage-operated attracted armature units of compact design, featuring

positive action and a high degree of mechanical stability. Voltage is applied to the relay

coils via an internal diode bridge which enables relays to be energised from AC or DC

power supplies.

Typical applications are for general contact multiplication, interlocking and customisation

to suit the substation.

Models

There are five versions of the MVAA relay, each with a different type of contact reset

mechanism:

MVAA 11

Single element relay with self reset contacts (Double element version is

type MVAA 21)

MVAA 13      Single element relay with hand reset contacts (Double element version is

type MVAA 23)

MVAA 14

Single element relay with electrical reset contacts

Contacts

Contacts are made from a silver/copper alloy, shaped and

positioned to ensure very reliable, low resistance operations.

Normal duty make, break and changeover contacts and heavy duty

magnetic blow-out contacts are available in various combinations

(see tables 1. 2 and 3).

Heavy duty magnetic blow-out contacts are recommended for

breaking heavy or highly inductive DC loads. When these are fitted,

the number of contacts available may be reduced (see table 3).

Breaking capacity curves for these contacts are shown in figure 1

MVAW

on next page.

Operation Indicators

Each relay element is supplied with an optional hand reset

operation indicator.

The indicator consists of a mask, which on operation drops to

expose a broad red strip positioned diagonally on a rectangular

white background

Technical Data

VOLTAGE RATING (V)

24/27

30/34

48/54

OPERATING VOLTAGE RANGE (V)

110/125

220/250

• Frequency: 50/60 Hz

• Withstand rating: The standard relay will withstand 120% of its

maximum voltage rating continuously. High speed variants with

time (where the 10th character of the model number is C or Q)

are short time rated. These must be energised for a maximum of

2 minutes or employ a break contact, wired externally, to cut off

the auxiliary supply after operation

•  Burdens: 3 W per element at all rated voltages

• Operating times: The operating times are typically 12-25 ms

depending on the number of contacts and relay type