ALSTOM PIB-100G Interface Board Module

Installation of the Hilscher System software

To install the Hilscher System software insert the installation CD into the appropriate

drive of the computer, the installation should auto run.

Should it fail to auto run, use Windows Explorer to select the installation program

“autorun.exe”. This will start the installation process and prompt you as to what actions

to take in order to install the required software and drivers.

The installation process will prompt you to select the component you require

You require the CIF Device Driver and your selected Fieldbus. All other options can be

de-selected to save disk space if required. For this example we have selected

PROFIBUS.

Select the required options then NEXT to continue.

Select an appropriate program folder location, NEXT to continue.

At this point installation will commence for the items you selected. You will be prompted

before each selection is installed

Start by inserting the Fieldbus master module. This represents the module installed in

GEM80-500.

To do so select – INSERT then MASTER

Position the master module at top of the line representing the network cable, the area

above enclosed by the rectangle, right click to drop.

Next select the required master module

MUST HAVE

1. Controlled release of the communication by application program

2. Byte addresses

3. Little Endian

4. Buffered, host controlled

The Watchdog Time can be adjusted to suit your application (default 1000ms). It

should not be set to a value  lower than twice the longest GEM80-500 Ladder scan

rate.

Once configured OK to return to network overview.

7.4.2

Inserting Slaves

To do so select – INSERT then SLAVE

Use the mouse to position slave on the line representing the network cable, right click

to drop