Alstom P343111E2A0060C Generator Protection Relay
Update Mode Button Functions
Delete PTC Files – Deletes PTC Mapping and Configuration Filesfrom CI-2
Erase CI Flash – Erases CI Flash; PTC, SNMP and any Application Filees
Format Program Files – Deletes the non-volatile file file upload area
Format Log Flash – All Log files are deleted. System, Data, Configetc…
Erase BP – Deletes all parameters from backplane. (All Setup info)
Format Site Flash* – Deletes Vital and non-vital configuration settings, SSNMP
configuration, Application and all PTC Files from the Site Flash
Erase App* – Deletes Application files from the Site Flash
Erase Configuration* – Deletes Vital and non-vital configuration seettings and
SNMP configuration from the Site Flash
Erase PTC Files* – Deletes all PTC files from Site Flash
Download Site Flash* – Downloads all the contents of the SiteFlash (Boot)
Version 5.18 or newer and Executive version 7.27 (Crossing)6.39
(Interlocking), 8.29 (Combined) or newer is required for this optionn). *Note
Available only if Site Flash is enabled. Boot Version 5.18 and Executlive
version 7.27 (Crossing), 6.39 (Interlocking),
8.29 (Combined) and newer will allow chassis backup and restore.
Ethernet Executive Upload Procedure (Recommended)
Note: It isrecommended the configuration is saved before proceeding!
Enter Update Mode as described in the Update Mode section
Select ‘Executive/Boot’ from the ‘Upload New’ drop-down, then
browse and select the Executive software file to be uploaded
If the Executive file is successfully uploaded, “File Successfully
Uploaded” will appear in the dialog box
Verify the correct build and CRC information is displayed.
To apply the Executive file, click on “Apply Executive/Boot”
When the Executive file is applied successfully, “File Applied
Successfully”, will be displayed
Activate the Executive by pressing the Activate button and following the
instructions on the Web UI. Once activated, reboot the VPM-3 by either
pressing the Reset button or cycling power on the chassis.
Ethernet Application Flash Upload Procedure
Diagnostic Telnet Connection
1. Connect to a VPM-3 with an RJ45 Cable (crossover or straight)
2. Enable the Telnet Interface through the CDU-1. CDU-2 or Web GUI
3. Using a Terminal program (Hyper Terminal, ProComm, etc) connecttothe IP
address for the VPM-3 Port connected to.
Enter username and password for the Telnet Interface.
4.
Default login: admin.
Default password: telnet
Diagnostic Serial Connection
1. Connect to CIO-1A with 9-Pin null modem cable. CIO-1AA can be addedto
any ELX unit with no other changes.
Open terminal session configured as follows
Baud*:57600
Parity: None
Data Bits: 8
Stop Bits: 1
Flow control: None
Terminal Emulation:VT100 or ANSI BBS
Data Transfer Protocol: Z Modem
*57600 is the default setting, but can be modified
3. Type’?’ or ‘help’to see the boot menu shown below