Having correctly installed and configured the Fieldbus modules it is then possible to

configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of

the use of this tool is beyond the scope of this manual, although an operation guide is

included in section 7. For full instructions refer to the Hilscher documentation provided

on the CD.

This Windows based tool can communicate with the Fieldbus module using a serial link

or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the

guide in section 7 follows this route.

The serial link method bypasses the GEM80-500 completely by communicating

directly with the Fieldbus module. This method is suitable for monitoring the network

operation but should not be used for system configuration downloading. As it

communicates directly, new system configurations will be downloaded whether or not

the host GEM80 controller is in a running or halted state.

The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module.  As a

result the GEM80 Ethernet module is able to examine the commands sent from the

SyCon tool before passing them to the associated Fieldbus module. The running state

of the host GEM80 is also examined by the Ethernet module, attempts to modify

important system parameters will be refused if the host GEM is in the running state.

This results in an error code of 170 at the SyCon tool. The TCP/IP method is also

suitable for monitoring the network operation.

See section 7 for further information on the operation of the SyCon tool

Exchange Mode

The Exchange Mode LS byte contains the communications state indicator in bit 0. This is

set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0.  The

remainder of the byte is reserved and is cleared to 0.

The Exchange Mode MS byte contains the process data handshake mode as configured

by SyCon.

• Value = 1. Bus synchronous, device controlled.

• Value = 2. Buffered, device controlled.

• Value = 3. Non-consistent, uncontrolled.

• Value = 4. Buffered, host controlled (recommended).

• Value = 5. Bus synchronous, host controlled.

The recommended setting is buffered host controlled. This will have the least impact on

the controller’s scan rate

REXROTH VT-HNC100-1-22/W-08-0-0
REXROTH VT-HNC100-1-22/W-08-C-0
REXROTH VT-HNC100-4-3X/P-I-00/G04 R901134617
REXROTH VT-VSPA1-1-11
REXROTH VT3000S34-R5
REXROTH VT3002-2X/48F
REXROTH VT3006S34R5
REXROTH VT3006S35R1
REXROTH VT3024
REXRTOH SYHNC100-NIB-22A/W-24-P-D-E23-A012 R900978416
REXRTOH SYHNC100-NIB-22A/W-24-P-D-E24-A012  R900978416
REXRTOH SYHNC100-NIB-23/W-24-P-D-E23-A012
REXRTOH SYHNC100-NIB-23/W-24-P-D-E23-A012 R900978416

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注