ALSTOM 029.155 562 Communication Module

System Configuration

Having correctly installed and configured the Fieldbus modules it is then possible to

configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of

the use of this tool is beyond the scope of this manual, although an operation guide is

included in section 7. For full instructions refer to the Hilscher documentation provided

on the CD.

This Windows based tool can communicate with the Fieldbus module using a serial link

or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the

guide in section 7 follows this route.

The serial link method bypasses the GEM80-500 completely by communicating

directly with the Fieldbus module. This method is suitable for monitoring the network

operation but should not be used for system configuration downloading. As it

communicates directly, new system configurations will be downloaded whether or not

the host GEM80 controller is in a running or halted state.

The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module.  As a

result the GEM80 Ethernet module is able to examine the commands sent from the

SyCon tool before passing them to the associated Fieldbus module. The running state

of the host GEM80 is also examined by the Ethernet module, attempts to modify

important system parameters will be refused if the host GEM is in the running state.

This results in an error code of 170 at the SyCon tool. The TCP/IP method is also

suitable for monitoring the network operation.

See section 7 for further information on the operation of the SyCon tool

Exchange Mode

Woodward 8290-191
Benninger FU10125A60
ABB UNS4881b,V.4 3BHE009949R0004
Honeywell CC-PAIH02
YOKOGAWA YTA110
STUCKE SYMAP-BCG 4512
24/1A/PT400V/D1/GC1/G1V400/RU0/C2/0/4/1/2
METSO ND9106HNT
HIRSCHMANN MM20-Z6Z6Z6Z6SBHH
GE FLC48SXC8V11A
Alstom 29.144463
Woodward UG‐25+
8528-300
METSO XWB11283-900N12
WESTRONICS SBGA-15P1WM
EMERSON FSFB-S600+ S600P1-0-B-0-0-1
GE IS200EDISG1AAA
Prosoft RLX2-IFH24E

The Exchange Mode LS byte contains the communications state indicator in bit 0. This is

set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0.  The

remainder of the byte is reserved and is cleared to 0.

The Exchange Mode MS byte contains the process data handshake mode as configured

by SyCon.

• Value = 1. Bus synchronous, device controlled.

• Value = 2. Buffered, device controlled.

• Value = 3. Non-consistent, uncontrolled.

• Value = 4. Buffered, host controlled (recommended).

• Value = 5. Bus synchronous, host controlled.

The recommended setting is buffered host controlled. This will have the least impact on

the controller’s scan rate