DEIF LSU-122DG Load sharing, paralleling & operation
LSU-122DG
Load sharing, paralleling & operation
DEIF’s load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).
DEIF’s load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).
Suitable for control of diesel and gas generators, for instance, they can control the power unit in stand-alone mode (performing frequency control) or parallel with other power units (performing frequency and power control).
The units have built-in power and frequency transducers that enable connection of external equipment. Constant power or isochronous mode is also possible. Speed control is conducted by two relays.
Variants
LSU-112DG
Frequency and power control
LSU-113DG
Frequency and power control
With -P>
LSU-114DG
Frequency and power control
With start/stop
LSU-122DG
Reactive
U and Q control
Features
Reactive. U and Q control
Built-in power and frequency transducer
Constant power or isochronous mode
LED indication of status
LED indication for activated control
35 mm DIN rail or base mountin
Function
The LSU-112DG is measuring the voltage and the
current from which the frequency and the power pro
duced by the power unit are measured. The built-in
power transducer is based on an I x cos phi principle.
The following couplings are available: – –
1W(4) – single phase
1W3 – 1-element 3-phase, 3-wire, balanced load
If unbalanced load can be expected, an external power
transducer with an output of 4 to 20 mA can be con
nected to the LSU-112DG. In this case the built-in I x
cos phi transducer is automatically interrupted.
The power and frequency measured by each LSU
112DG are fed to two paralleling lines for comparison
with the frequency (FS) and power (PS) of the other
connected LSU-112DG.
If L1 or L2 is disconnected from the LSU-112DG at the
same time as a power unit in a power plant is discon
nected from the power line (busbar), built-in relays in
the LSU-112DG ensure that the power output and the
frequency output of the associated unit are disconnect
ed from the paralleling lines. Likewise the power and
frequency outputs are disconnected if the auxiliary
voltage to the LSU-112DG is disconnected.