DEIF

DEIF LSU-114DG Load sharing, paralleling & operation

LSU-114DG

Load sharing, paralleling & operation

DEIF’s load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).

DEIF’s load sharing units offer load sharing in various ways between generators and interfaces to a governor through an electronic potentiometer (EPQ96-2 or EPN110DN).

Suitable for control of diesel and gas generators, for instance, they can control the power unit in stand-alone mode (performing frequency control) or parallel with other power units (performing frequency and power control).

The units have built-in power and frequency transducers that enable connection of external equipment. Constant power or isochronous mode is also possible. Speed control is conducted by two relays.

Variants

LSU-112DG

Frequency and power control

LSU-113DG

Frequency and power control

With -P>

LSU-114DG

Frequency and power control

With start/stop

LSU-122DG

Reactive

U and Q control

Features

Frequency and power control. With start/stop

Built-in power and frequency transducer

Constant power or isochronous mode

LED indication of status

LED indication for activated control

35 mm DIN rail or base mountin

Application

The LSU-112DG is a control unit for control of the prime

mover in a power unit.

The LSU-112DG can control the power unit  –  –  –

in stand-alone mode, performing frequency control

parallel with grid, performing power control

parallel with other power units, performing frequen

cy and power control

The unit is designed for connection to a mechanical

speed governor, however in conjunction with the DEIF

electronic potentiometer type EPN-110DN or EPQ-96 it

can control electronic speed governors as well.

The LSU-112DG has a built-in frequency transducer. If

a very stable frequency is wanted, an external frequen

cy transducer common for all the LSU-112DGs in the

power plant can be connected. If a number of power

units are to be synchronised to the busbar at the same

time, the frequency may likewise be controlled external

ly.