SAUTER Valve actuator ASM 105/115 series ASM105F120

SAUTER  Valve actuator ASM 105/115 series ASM105F120

ASM 105. 115: Damper actuator

How energy efficiency is improved

Time-dependent cut-off facility for efficient usage of energy

Features

• For controllers with switching output (2- and 3-point)

• Self-centring spindle adapter

• Gear unit can be disengaged to position the damper and for manual adjustment

• Synchronous motor with electronic activation and cut-out

•Maintenance-free

• Suitable for all fitting positions

Technical data

Parameters

Angle of rotation Max. 95°

Admissible damper shaft Ø 8…16 mm, □ 6.5…12.5 mm

Admissible damper shaft (hardness) Max. 300 HV

Operating noise < 30 dB (A)

Response time 200 ms

Ambient conditions

Admissible ambient temperature1)–20…65 °C

Admissible ambient humidity 5…85% rh, no condensation

Function

Control 2-/3-point

Construction

Weight 0.7 kg

Housing Lower section black, upper section

yellow

Housing material Fire-retardant plastic

Power cable 1.2 m long, 3 × 0.75 mm²

Standards and directives

Type of protection IP54 (EN 60529)

Protection class 24 V III (EN 60730)

Protection class 230 V II (EN 60730)

CE conformity according to EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-2

EN 61000-6-3. EN 61000-6-4

Directive 2006/95/EC EN 1050

Low-Voltage Directive 2014/35/EU2) EN 60730-1. EN 60730-2-14

Over-voltage category III

Degree of contamination II

Overview of types

Type Rotational torque and

holding torque

Running time for 90° Power supply Power consumption

ASM105F100 5 Nm 30 s 230 V~ 2.4 W, 5.4 VA

ASM105F120 5 Nm 120 s 230 V~ 2.0 W, 5.0 VA

ASM105F122 5 Nm 120 s 24 V~ 1.6 W, 1.7 VA

ASM115F120 10 Nm 120 s 230 V~ 2.0 W, 5.0 VA

ASM115F122 10 Nm 120 s 24 V~ 1.6 W, 1.7 VA

Accessories

Type Description

0361977002 Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105. 115

0372145001 Auxiliary change-over contacts, single

1) Operating time approx. 80% up to 65 °C, 100% up to 55 °C

2) Only for ASM1*5F1*0

Type

0372145002

0372286001

0372286002

0372286003

0372300001

0372301001

0372320001

0372459100

0372459102

51.040

GE 04220FL11232A
MOOG G122-829A001
ABB REF545KB133AAAA
Baslar DECS-250-CN1SN1N
ABB REF620 NBFNAANNNEA1BNN1XF
ABB 1TGE120021R0810
Brad DRL-DPM-BKF
GE IS200WROBH1A
WOODWARD PEAK200 8200-1509
ALSTOM EP3-F-4
Woodward 8290-191
Benninger FU10125A60
ABB UNS4881b,V.4 3BHE009949R0004
Honeywell CC-PAIH02
YOKOGAWA YTA110
STUCKE SYMAP-BCG 4512
24/1A/PT400V/D1/GC1/G1V400/RU0/C2/0/4/1/2

Description

Auxiliary change-over contacts, double

Potentiometer, 130 Ω

Potentiometer, 1000 Ω

Potentiometer, 5000 Ω

Torsion protection, long (230 mm)

Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.

Hexagon key as visualisation for position indicator

External switching, 230 V version for parallel operation with A*M or actuators with limit switch,

incl. junction box

External switching, 24 V version for parallel operation with A*M 1*4 or drives with limit switch,

incl. junction box

A Auxiliary change-over contacts: Infinitely variable 0…90°, admissible load 5(2) A, 24…230 V

A Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator

Description of operation

When voltage is applied to the cable, the control unit to be activated is moved to any desired position.

Direction of rotation for 3-point control (viewing the spindle adaptor from the actuator):

• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable.

• The spindle adaptor turns in the anti-clockwise direction, with the voltage on the black cable.

Direction of rotation for 2-point control (viewing the spindle adaptor from the actuator):

There is always voltage on the black cable.

• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable.

• The spindle adaptor turns in the anti-clockwise direction, with no voltage on the brown cable.

In the end positions (limit stop in air damper or maximum angle of rotation reached), or in the case of

an overload, the magnetic coupling is activated. The positioning signal is switched off by the electron

ic cut-out after 3 minutes or 60 seconds (F100). The effective end position results from the limit stop

of the damper or the angle-of-rotation limit, or by reaching the maximum angle of rotation of 95°.

The manual adjustment is performed by releasing the gear unit using the adjuster beside the connec

tion cable and simultaneously adjusting the spindle adaptor.

With 3-point control, the direction of rotation is changed by swapping the connections.