SAUTER Valve actuator ASM 105/115 series ASM105F10
Valve actuator ASM 105/115 series ASM105F10
ASM 105. 115: Damper actuator
How energy efficiency is improved
Time-dependent cut-off facility for efficient usage of energy
Features
• For controllers with switching output (2- and 3-point)
• Self-centring spindle adapter
• Gear unit can be disengaged to position the damper and for manual adjustment
• Synchronous motor with electronic activation and cut-out
•Maintenance-free
• Suitable for all fitting positions
Technical data
Parameters
Angle of rotation Max. 95°
Admissible damper shaft Ø 8…16 mm, □ 6.5…12.5 mm
Admissible damper shaft (hardness) Max. 300 HV
Operating noise < 30 dB (A)
Response time 200 ms
Ambient conditions
Admissible ambient temperature1)–20…65 °C
Admissible ambient humidity 5…85% rh, no condensation
Function
Control 2-/3-point
Construction
Weight 0.7 kg
Housing Lower section black, upper section
yellow
Housing material Fire-retardant plastic
Power cable 1.2 m long, 3 × 0.75 mm²
Standards and directives
Type of protection IP54 (EN 60529)
Protection class 24 V III (EN 60730)
Protection class 230 V II (EN 60730)
CE conformity according to EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-2
EN 61000-6-3. EN 61000-6-4
Directive 2006/95/EC EN 1050
Low-Voltage Directive 2014/35/EU2) EN 60730-1. EN 60730-2-14
Over-voltage category III
Degree of contamination II
Overview of types
Type Rotational torque and
holding torque
Running time for 90° Power supply Power consumption
ASM105F100 5 Nm 30 s 230 V~ 2.4 W, 5.4 VA
ASM105F120 5 Nm 120 s 230 V~ 2.0 W, 5.0 VA
ASM105F122 5 Nm 120 s 24 V~ 1.6 W, 1.7 VA
ASM115F120 10 Nm 120 s 230 V~ 2.0 W, 5.0 VA
ASM115F122 10 Nm 120 s 24 V~ 1.6 W, 1.7 VA
Accessories
Type Description
0361977002 Assembly materials for M3R, M4R, MH32R/F, MH42R with ASM 105. 115
0372145001 Auxiliary change-over contacts, single
1) Operating time approx. 80% up to 65 °C, 100% up to 55 °C
2) Only for ASM1*5F1*0
Type
0372145002
0372286001
0372286002
0372286003
0372300001
0372301001
0372320001
0372459100
0372459102
51.040
Description
Auxiliary change-over contacts, double
Potentiometer, 130 Ω
Potentiometer, 1000 Ω
Potentiometer, 5000 Ω
Torsion protection, long (230 mm)
Spindle adaptor for squared end hollow profile (x 15 mm), pack of 10 pcs.
Hexagon key as visualisation for position indicator
External switching, 230 V version for parallel operation with A*M or actuators with limit switch,
incl. junction box
External switching, 24 V version for parallel operation with A*M 1*4 or drives with limit switch,
incl. junction box
A Auxiliary change-over contacts: Infinitely variable 0…90°, admissible load 5(2) A, 24…230 V
A Potentiometers: Only one potentiometer or one set of auxiliary contacts can be fitted for each actuator
Description of operation
When voltage is applied to the cable, the control unit to be activated is moved to any desired position.
Direction of rotation for 3-point control (viewing the spindle adaptor from the actuator):
• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable.
• The spindle adaptor turns in the anti-clockwise direction, with the voltage on the black cable.
Direction of rotation for 2-point control (viewing the spindle adaptor from the actuator):
There is always voltage on the black cable.
• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable.
• The spindle adaptor turns in the anti-clockwise direction, with no voltage on the brown cable.
In the end positions (limit stop in air damper or maximum angle of rotation reached), or in the case of
an overload, the magnetic coupling is activated. The positioning signal is switched off by the electron
ic cut-out after 3 minutes or 60 seconds (F100). The effective end position results from the limit stop
of the damper or the angle-of-rotation limit, or by reaching the maximum angle of rotation of 95°.
The manual adjustment is performed by releasing the gear unit using the adjuster beside the connec
tion cable and simultaneously adjusting the spindle adaptor.
With 3-point control, the direction of rotation is changed by swapping the connections.