SAUTER Linear valve actuator AVM 105S/115S series AVM105SF132

AKM 105S, 115S: Rotary actuator with SAUTER Universal

Technology (SUT) for ball valve

How energy efficiency is improved

Automatic adaptation to ball valve, precise activation and high energy efficiency with minimal operat

ing noise.

Features

• For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA,

(AKM115S) and 6-way ball valve B2KL

• For controllers with constant output (0…10 V) or switching output (2-/3-point control)

• Assembly with ball valve without the use of tools

• Stepping motor with SAUTER Universal Technology (SUT) electronic control unit

• Electronic force-dependent motor cut-off

• Automatic recognition of applied control signal (continuous or switched)

• Coding switch for selection of characteristic and running time (35 s, 60 s, 120 s)

• Type of characteristic (linear/quadratic/equal-percentage) can be set on the actuator

• Direction of operation can be selected directly on the cable

•Maintenance-free gear unit

• Gear unit can be disengaged in order to position the ball valve manually (using the lever)

• Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve

Technical data

Power supply

Power supply 24 V~ ±20%, 50…60 Hz

Power supply 24 V=-10%…20%

Power consumption 4.9 W/8.7 VA

Parameters

Running time1) 35/60/120 s

Angle of rotation 90°

Response time 200 ms

Power cable 1.2 m, 5 × 0.5 mm2

Positioner Positioning signal y 0…10 V, Ri > 100 kΩ

Positional feedback signal 0…10 V; load > 10 kΩ

Starting point U0 0 V or 10 V

Control span ΔU 10 V

Switching range Xsh 200 mV

Ambient conditions

Temperature of medium2) Max. 100 °C

Admissible ambient temperature–10…55 °C

Admissible ambient humidity 5…95% rh, no condensation

Construction

Fitting Vertically upright to horizontal,

not upside down

Weight 0.7 kg

Housing Lower section black, upper section

yellow

Housing material Fire-retardant plastic

Standards and directives

Type of protection IP54 as per EN 60529

Protection class III as per IEC 60730

CE conformity according to EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-3

EN 61000-6-4

Overview of types

51.364

Type

Torque

AKM105SF132 4 Nm

AKM115SF132 8 Nm

Accessories

Type

0313529001

0372462001

0510420001

0510240011

0510480001

0510480002

Description

ABB 81943A059-2
ABB A419471
ABB AINT-14C
bently 3500/92-02-01-01
bently 3500/32-01-01
bently 3500/33-01-01
bently 3500/25-01-01-00
bently 3500/40M-01-01
bently 3500/22M-01-02-01
Meggitt CA202 – 144-202-000-203
Meggitt TQ402 – 111-402-000-012
bently 3500/92-02-01-01
bently 3500/32-01-01
bently 3500/33-01-01
bently 3500/25-01-01-00
bently 3500/40M-01-01
bently 3500/22M-01-02-01

Split-range unit for adjusting sequences, fitted in separate junction box

CASE Drives PC tool for configuring the drives by computer

Adaptor required when temperature of the medium > 100 °C

Adaptor required when temperature of the medium < 5 °C

Auxiliary change-over contacts, single

Auxiliary change-over contacts, double

A Auxiliary change-over contacts: Infinitely variable 0…100%, admissible load 5(2) A, 24…230 V

Description of operation

Depending on the type of connection (see connection diagram), the actuator can be used as a contin

uous 0…10 V, 2-point (OPEN/CLOSE) or 3-point actuator with an intermediate position

(OPEN/STOP/CLOSE).

The running time of the actuator can be set with the coding switch according to requirements. The

coding switch can be used to select the equal-percentage, linear or quadratic characteristic. The

AKM 115 is combined with ball valves that have an equal-percentage basic characteristic like the

VKR or BKR.

The manual adjustment is performed by releasing the gear unit (slide switch beside the connection

cable) and simultaneously turning it with the lever. The actuator position can be determined by look