SAUTER

SAUTER AVM115F901 Linear Valve Actuator

AVM 105. 115: Valve actuator

How energy efficiency is improved

Torque-dependent cut-off facility for efficient usage of energy

Features

• Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series

• For controllers with a switching (2-/3-point) output

• Synchronous motor with electronic control unit and time-dependent cut-off

• Direction of operation can be selected directly on the cable

•Maintenance-free gearbox with magnetic coupling

• Gear unit can be disengaged in order to position the valve by hand (hexagon key provided)

• Connection with valve spindle performed automatically

• Cap nut for valve fitting made of brass

• Fitting vertically upright to horizontal, not suspended

necting the voltage to terminals MM/N and 01. When dismantling, first the actuator and valve spindles

are released, then the cap nut. The device is delivered ex works in the middle position.

The concept of synchronous motor and magnetic coupling enables parallel operation of multiple valve

actuators of the same type.

The maximum accessory equipment for an actuator is 1 auxiliary change-over contact or 1 potentiom

eter.

GE MMLG01
GE MMLG02
GE MMLB01
GE MVAJ105RA0802A
GE IS200TRPGH1B
ABB PCD231 3BHE025541R0101
ABB PCD235 3BHE032025R0101
AMC P111-6052
MOOG D635-706
ABB SCA022657R8790 CU2A01V2
CTI 2500-C200
GE IS200ESYSH1AAA
GE IS200EDISG1AAA
SAUTER AVM234SF132-5
ABB SCC-C 23070-0-10311111
METSO PDP401
Brad Communications DRL-DPM-BKF
ABB 3BSE027062R50 PFCL 201CE-50kN

The auxiliary contact accessory is screwed onto the top cover of the actuator. To be able to make the

mechanical connection, you first have to remove the indicator knob. A new indicator can be seen on

the cover of the accessory.

Additional technical data

The upper section of the housing with the cover and indicator knob contains the synchronous motor

with capacitor.

The lower section of the housing contains the maintenance-free gear unit and the gear-release knob.

Auxiliary change-over contacts:

• Switch rating max. 230 V VAC, current min. 20 mA at 20 V

• Switch rating max. 4…30 V VDC, current 1…100 mA

Power consumption

Type

Running time [s]

Status

AVM105F100

30

Operation

AVM105F120

120

Operation

AVM105F122

120

AVM115F120

120

AVM115F122

120

Outdoor installation

Operation

Active power P [W]

Apparent power S [VA]

2.4

5.4

2.0

5.0

1.6

1.7

Operation

2.0

5.0

Operation

1.6

1.7

The actuators must also be protected from the weather if they are installed outside the building.

Disposal

When disposing of the product, observe the currently applicable local laws.

More information on materials can be found in the Declaration on materials and the environment for

this product.