The MP-3000 Motor Protection Relay has been designed for maximum

motor utilization and protection. It is desirable to run the motor as

close as possible to its design limits, while protecting it against exces

sive heating and damaging overload conditions. The MP-3000 has

EATON 101073735-001 LEG MODULE BOARD, PENT w/ 100A

ield-proven protection algorithms developed from basic motor design

principles and operating parameters.

The MP-3000 protects against rotor and stator overheating, short

circuits or insulation faults, excessive starting duty, and abnormal

operating conditions.

2.1.1 Intel-I-Trip (adaptive I2t Motor Overload Protection)

Motor operation is typically limited by the rotor thermal capabilities, but

the measuring quantities are stator currents. This requires accurate

measurements and good motor thermal models to provide maximum

utilization and reliable protection.

The MP-3000 uses the field-proven Intel-I-Trip overload measure

ment and motor thermal protection model that uses the manufacturer’s

nameplate data to develop an overload protection curve specifically for

the motor being protected. When RTDs are used, the Intel-I-Trip over

load protection curve becomes adaptive.  The overload trip times will

change based on the modeling impact of the motor’s internal tempera

ture data.  It also trips directly for high stator temperature.

The relay samples the current waveforms 36 times per cycle provid

ing accurate measurements of the positive and negative sequence

currents, as well as harmonic components that add to rotor and stator

heating. The negative sequence component of current causes far

greater heating effect on the rotor and has a greater impact on the

thermal model in the relay, as compared to the balanced or positive

sequence component.

2.1.2 Instantaneous Overcurrent Protection

The MP-3000 has an instantaneous phase overcurrent function to trip

the motor for fault currents, sometimes saving the fuses for medium

current faults.  This function can be disabled and has an adjustable

start time delay on starting to avoid nuisance tripping on inrush.

2.1.3 Phase Current Unbalance Protection

Motor supply circuits are often fed through fuses and may be ener

gized with one fuse blown, causing single phasing of the motor.  The

MP-3000 measures the current unbalance and can be used to alarm

or trip the motor before heating and a thermal-model trip.  Pickup, start

and run timers, and separate alarm settings are provided.

2.1.4 Ground fault Protection

A separate monitoring circuit is used to measure ground current.  A

zero sequence ground CT is recommended for more sensitive protec

tion against winding insulation failure to ground.  The relay ground CT

input can be connected residually from the three phase CTs, but with

much inferior protection sensitivity.  The ground fault protection has

adjustable pickup and time delay set points, or it can be disabled.

3 MP-3000 Motor Protection Relay accessories.

Catalog Number Description Style Number

URTD Module Universal RTD Module 2D78559G01

IQDCPS IQ DC dc to ac power supply converter, 100 – 150 Vdc 2D78542G01

MPFO-1 1 Meter precut optical fiber link for URTD with connectors 66D2037G01

MPFO-5 5 Meter precut optical fiber link for URTD with connectors 66D2037G02

MPFO-10 10 Meter precut optical fiber link for URTD with connectors 66D2037G03

MPFO-25 25 Meter precut optical fiber link for URTD with connectors 66D2037G04

MPFO-50 50 Meter precut optical fiber link for URTD with connectors 66D2037G07

MPFO-75 75 Meter precut optical fiber link for URTD with connectors 66D2037G10

MPFO-76 76 Meter precut optical fiber link for URTD with connectors 66D2037G11

MPFO-100 100 Meter precut optical fiber link for URTD with connectors 66D2037G13

MPFO-120 120 Meter precut optical fiber link for URTD with connectors 66D2037G14

MP3BRACKET PONI Mounting Bracket 66D2053G01

MPML Relay mounting plate adapter with 1/2” Stud – fits GE Multilin® 269 cutout 66D2044G01

MPML-L Relay mounting plate adapter with 1” Stud – fits GE Multilin® 269 cutout 66D2044G02

EPONI Ethernet communications module 66D2028G01

EPONIF Ethernet optical fiber communications module 66D2028G02

IPONI INCOM communications module 8793C36G03

DPONI Data communications module 6D2132G01

RS-485 PONI Modbus RTU communications module 66D2042G01

MD3000 Motor/Generator Differential Relay Fixed Case 66D2126G01

MD3001 Motor/Generator Differential Relay Drawout Case 66D2127G01

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注