EPDGP I/O boards (see Figures 2-10 and 2-11) interface nearly all the peripherals of the

Enhanced Micro TDC3000 Control System.  You are now going to connect those cables

which could not be installed at the factory

The EPDGC I/O is the EMC Directive board version used to interface with the monitor,

keyboard, touchscreen, SCSI cartridge drives and printers.  The EMC Directive version is

shown in Figures 2-12 and 2-13.  All the connectors have been converted to D-type

connectors with full 360 degree shielding.  The connectors are bulkhead mounted into the

board face plate which provides a contiguous shield from module to cable.  The cabling of

peripheral devices are connected at this face plate.  The Touchscreen and Trackball cables

are connected to the cabinet bulkhead shown in Figure 2-7.

The background color of the monitor can be selected as one of four colors as shown in

Figure 2-13.  The pinning shown is for the default background color.  Pin the board for

desired background color.  The pinned background color selection is only in force until the

station is loaded with software.

The sync pulse requirements of the monitor used is pinned at J6 (factory set) as shown in

Figure 2-13.  The pinning of J6 will determine the tab number of the board and is factory

set.  The monitor sync pulse source will either be direct (Tab 100) or inverted (Tab 200)

Operator Keyboard Cabling

Connect the keyboard cable to the connector on the face plate of the EPDGC I/O board (see

Figure 2-11).  Use a small screwdriver to tighten the screws (2) on the connector.

2.7.6  Printer Cabling

The printer cable (51303631-003) has similar connectors on each end.

1. Connect the end of the cable marked PIC to the connector on the face plate of the

EPDGC I/O board marked PRINTER in Figure 2-11.  Use a small screwdriver to tighten

the screws (2) on the connector.

2. Connect the other end of the printer cable (marked PRINTER) to the back of the printer.

Using a small screwdriver, tighten the screws (2) on the connector.

2.7.7  Color Monitor Cabling

Connect the cable from the color monitor to the EPDGC I/O face plate connector marked

VIDEO in Figure 2-11. on the upper transition panel.  Using a small screwdriver, tighten

the screws (2) on the connector.  Finally, attach the power cord to the monitor and plug it

in.

ABB REF601CE446BB1NH 24-240V 50/60Hz
ABB UFC765AE102 3BHE00364R0102
bently 3500/60
PROCONTROL P GJR2395500R1210 83SR50
PROCONTROL P 5102-MCM4-DFCM4
ABB 81943A059-1
ABB 81943A059-2
ABB A419471
ABB AINT-14C
bently 3500/92-02-01-01
bently 3500/32-01-01
bently 3500/33-01-01
bently 3500/25-01-01-00
bently 3500/40M-01-01
bently 3500/22M-01-02-01
Meggitt CA202 – 144-202-000-203
Meggitt TQ402 – 111-402-000-012
bently 3500/92-02-01-01
bently 3500/32-01-01
bently 3500/33-01-01
bently 3500/25-01-01-00
bently 3500/40M-01-01
bently 3500/22M-01-02-01
bently 26530-12-10-02-018-038-22-04-00
bently 3500/15-05-05-01 106M1079-01 +106M1081-01

2.7.8  Engineer’s Keyboard Cabling

Insert the plug on the cable from the engineer’s keyboard into the small connector located

on the right of the operator keyboard.  Note the plug will only fit one way.

2.7.9 TPLCN Cabling

The two (2) TPLCN cables (51304505-100) have similar connectors on each end.  The

standard cable length is 5 feet (1.5 meters).  The optional cable (Option number

MX-MTLC11) is 33 feet (10 meters) long, allowing a maximum distance between towers

of 10 meters.  The cable set connects directly to the TP-485 board face plates in the towers.

1. Attach one cable plug to the TP-485 face plate connector marked BUS A and the other

cable plug to BUS B at the rear of Tower #1.  Using a small screwdriver, tighten the

screws (2) on the connectors.

2. Attach the other end of the cable to the TP-485 face plate connector marked BUS A and

the other cable plug to BUS B at the rear of Tower #2.  Use a small screwdriver to

tighten the screws (2) on the connectors.

3. Attach the ground wires to the small screws, if they are on your cable