Alarm Types

Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)

Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

To use alarm 1. set the output assignment to alarm 1.

Set

value Alarm type

Alarm output operation

Description of function When alarm value X

is positive

When alarm value X

is negative

0 Alarm function OFF Output OFF No alarm

1 Upper- and lower-limit *1 *2

Set the upward deviation in the set point for the alarm upper

limit (H) and the lower deviation in the set point for the alarm

lower limit (L). The alarm is ON when the PV is outside this

deviation range.

2

(default) Upper-limit

Set the upward deviation in the set point by setting the alarm

value (X). The alarm is ON when the PV is higher than the

SP by the deviation or more.

3 Lower-limit

Set the downward deviation in the set point by setting the

alarm value (X). The alarm is ON when the PV is lower than

the SP by the deviation or more.

4 Upper- and lower-limit

range *1 *3

Set the upward deviation in the set point for the alarm upper

limit (H) and the lower deviation in the set point for the alarm

lower limit (L). The alarm is ON when the PV is inside this

deviation range.

5 Upper- and lower-limit with

standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit

alarm (1). *6

6 Upper-limit with standby

sequence A standby sequence is added to the upper-limit alarm (2). *6

7 Lower-limit with standby

sequence A standby sequence is added to the lower-limit alarm (3). *6

8 Absolute-value upper

51454473-175 Power   System Cage (Conformal Coated) HONEYWELL
51454470-175 Power System Cage (Conformal   Coated) HONEYWELL
RH914XL FBM212 Thermocouple/mV   Differential Input Module FOXBORO
5484-803 Woodward 200 mA Woodward 2CH   Actuator Controller Model
1794-OW8 Allen-Bradley Flex IO relay   output module
51308371-175 Digital Output Module   HONEYWELL
51308386-175 Digital Input Module   HONEYWELL
51308353-175 Experion Series-C I/O   HONEYWELL
51308365-175 Experion Series-C I/O   HONEYWELL
51308363-175 Analog Input Module   HONEYWELL
51308301-175 CF9 Control Firewall   Input/Output Termination Assembly (IOTA) HONEYWELL
51405047-175 Control Firewall Module   HONEYWELL
CC-TCNT01 51308365-175 HONEYWELL Input   Output Termination Assembly (IOTA)
NI-9234 NI Sound and Vibration Input   Module
20AD014A3AYNANNN Allen-Bradley 10   horsepower rated drive
1783-BMS10CGN Allen-Bradley Stratix 5700   Ethernet managed switch

The alarm will turn ON if the process value is larger than the

alarm value (X) regardless of the set point.

9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller than the

alarm value (X) regardless of the set point.

10

Absolute-value upper

limit with standby

sequence

A standby sequence is added to the absolute-value upper

limit alarm (8). *6

11 Absolute-value lower-limit

with standby sequence

A standby sequence is added to the absolute-value lower

limit alarm (9). *6

12 LBA (alarm 1 type only)-*7

13 PV change rate alarm-*8

14 SP absolute-value

upper-limit alarm

This alarm type turns ON the alarm when the set point (SP)

is higher than the alarm value (X).

15 SP absolute-value

lower-limit alarm

This alarm type turns ON the alarm when the set point (SP)

is lower than the alarm value (X).

16 MV absolute-value

upper-limit alarm *9

Standard Control Standard Control

This alarm type turns ON the alarm when the manipulated

variable (MV) is higher than the alarm value (X). Heating/Cooling

Control (Heating MV)

Heating/Cooling

Control (Heating MV)

Always ON

17 MV absolute-value

lower-limit alarm *9

Standard Control Standard Control

This alarm type turns ON the alarm when the manipulated

variable (MV) is lower than the alarm value (X). Heating/Cooling

Control (Cooling MV) Heating/Cooling

Control (Cooling MV)

Always ON​