ALSTOM 029.203 365 Keyboard Identification Number
Access to Other Menus (P1.31)
Menu 2 Parameter 02
As shipped, only Menu 1 is accessible. Access to other menus is controlled by the value entered into
parameter P1.31 that determines the menus that can be displayed by the Keypad. Three levels of access
are provided:
P1.31 value
Access level
Show Menu 1 only (by default, only Menu 1 is shown)
As specified by Menu 98 (user chooses the menus to be open)
2 All menus open
Access to P1.31 is controlled by passwords.
Security Passwords
To prevent inadvertent or unauthorised access to parameters, GE Power Conversion provides two levels of
security. They are known as Operator and Engineer levels, and each is accessed by a password (4-digit
code) that can be entered to allow an authorised operator or engineer to change parameter values. These
codes are numbers set in parameters P99.07 (operator security code) and P99.08 (engineer security code).
When editing is completed entering a value, other than the operator or engineer codes, in P99.06. locks the
parameters.
At default, the operator and engineer passwords are both open.
The parameters concerned with the editing and use of security passwords are described in Section 6.57.7.
Returning to Factory Default Settings
Record the settings in “Edit Review Mode” i.e. set P35.03 = 1.
If incorrect data is entered during commissioning, the factory default settings can be regained using the
following procedure:
Set parameter P1.31 = 2.
Navigate to P35.03 and edit its value to 1. to set up a review of edits.
Press to scroll through the current user edits; note these values.
When P35.03 re-appears all user edits have been displayed. Change P35.03 back to 0.
Navigate to P99.06 (see 6.62.7) and enter the password for engineer access.
Set P99.17 = 1 and press
The drive will now be at default settings.
Complete Menu Listing
A complete list of menus is shown in Table 3-1.
These menus are described in associated product documentation:
Menus 59. 60. 61 and 62 are described in the CANopen product manual;
Menus 58. 65. 66 and 67 are described in the 2nd CAN Port Manual;
Menu 63 is described in the DeviceNet manual; Menus 74 and 75 are described in the
PROFIBUS Manual;
Menu 78 is described in the MicroPEC™ Instruction Sheet; Menus 80. 83. 84. 85 and 89 are
described in documentation supplied with FIP Fieldbus cards.
Menus 50. 51. 52. 53 and 56 are specific to the SFE and are listed in Sections 4. 5 and 6.
In SFE Mode, only the shaded menus are visible