ALSTOM

Alstom MD2000 Operating Device

RECALLING A PARAMETER SET FROM A DRIVE DATA MANAGER™

The  MV3000e MicroCubicle™ and the  MV3000e DELTA AC Drives incorporate a feature to enable the

transfer of parameters from one drive to another via the  Drive Data Manager™ (where the Parameter Set

can be saved).  This feature is invoked via Parameter P99.16 – Backup Parameter – see Section 6.57.11.

Recalling a Parameter Set from one drive to another is a very powerful and useful feature.  However, care

must be taken to ensure that an incorrect Parameter Set in the target drive does not result from copying

the Parameter Set from an inappropriately configured drive, particularly from a drive of different rating from

the source drive.  It is therefore recommended that reference be made to the additional guidance in ‘Notes

for Recalling a Parameter Set from the Drive Data Manager™ (Keypad)’ in Section 6.57.11.

PARAMETER OVERVIEW

INTRODUCTION

The  MV3000e is controlled by means of parameters that are conveniently grouped into menus to form a

Menu Structure.

MENUS AND PARAMETERS

Parameters

The  MV3000e software uses system constants, scaling factors and other data (collectively referred to as

PARAMETERS) arranged into MENUS for ease of use.  Menus group parameters by like function e.g. Menu 6 is

Ramp Settings.  The complete menu listing is shown in Table 3-1.

Every parameter has a unique Parameter Number comprising a designator (prefix) P, followed by the menu

number and the number of the parameter, separated by a decimal point.  For example the MOTOR FULL

LOAD CURRENT parameter in Menu 2 has the Parameter Number P2.02 – see below