GE

GE MVAA23 Dual-element Manual Reset Auxiliary Relay

The MVAA is a low burden

Control and monitoring

auxiliary relay for

The relay can be supplied fitted with normal duty contacts and/or with hheavy

schemes demanding

duty blow-out contacts

several contacts for event

MVAA relays are voltage-operated attracted armature units of compactdesign

recording, alarm initiation,

featuring positive action and a high degree of mechanical stabillity. Voltage is

applied to the relay coils via an internal diode bridge which enables relabe

contact logic

energised from AC or DC power supplies.

arrangements, etc.

Typical applications are for general contact multiplication, interlocking and

customisation to suit the substation.

MODELS

There are five versions of the MVAA

relay, each with a different type of

contact reset mechanism:

MVAA 11

GE 531X304IBDARG1
GE 531X304IBDASG1
GE 531X305NTBAJG1
GE 531X305NTBANG1
GE 531X305NTBAPG1
GE 531X307LTBAFG1
GE 531X307LTBAHG1
GE 531X307LTBAJG1
GE 531X307LTBAKG1
GE 531X309SPCAJG1
GE 531X310NDAEG1
GE 531X305NTBANG1

Single element relay with

self reset contacts (Double

element version is type MVAA 21).

MVAA12

Single element relay with a

combination of self and hand reset

contacts (Double element version

is typeMVAA22).

MVAA 13

Single element relay with

hand reset contacts (Double

element version is type MVAA 23).

MVAA 14

Single element relay with

electrical reset contacts.

MVAA 15

Single element relay with

hand and electrical reset contacts.

The contacts can be reset either

electrically or by hand.

Contacts

Contacts are made from a silver/copper alloy, shaped and

positioned to ensure very reliable, low resistance operations.

Normal duty make, break and changeover contacts and heavy duty

magnetic blow-out contacts are available in various combinations

(see tables 1. 2 and 3).

Heavy duty magnetic blow-out contacts are recommended for

breaking heavy or highly inductive DC loads. When these are fitted,

the number of contacts available may be reduced (see table 3).

Breaking capacity curves for these contacts are shown in figure 1

on next page.

Operation Indicators

Each relay element is supplied with an optional hand reset

operation indicator.

The indicator consists of a mask, which on operation drops to

expose a broad red strip positioned diagonally on a rectangular

white background.