GE MVAA23 Dual-element Manual Reset Auxiliary Relay
The MVAA is a low burden
Control and monitoring
auxiliary relay for
The relay can be supplied fitted with normal duty contacts and/or with hheavy
schemes demanding
duty blow-out contacts
several contacts for event
MVAA relays are voltage-operated attracted armature units of compactdesign
recording, alarm initiation,
featuring positive action and a high degree of mechanical stabillity. Voltage is
applied to the relay coils via an internal diode bridge which enables relabe
contact logic
energised from AC or DC power supplies.
arrangements, etc.
Typical applications are for general contact multiplication, interlocking and
customisation to suit the substation.
MODELS
There are five versions of the MVAA
relay, each with a different type of
contact reset mechanism:
MVAA 11
| GE | 531X304IBDARG1 |
| GE | 531X304IBDASG1 |
| GE | 531X305NTBAJG1 |
| GE | 531X305NTBANG1 |
| GE | 531X305NTBAPG1 |
| GE | 531X307LTBAFG1 |
| GE | 531X307LTBAHG1 |
| GE | 531X307LTBAJG1 |
| GE | 531X307LTBAKG1 |
| GE | 531X309SPCAJG1 |
| GE | 531X310NDAEG1 |
| GE | 531X305NTBANG1 |
Single element relay with
self reset contacts (Double
element version is type MVAA 21).
MVAA12
Single element relay with a
combination of self and hand reset
contacts (Double element version
is typeMVAA22).
MVAA 13
Single element relay with
hand reset contacts (Double
element version is type MVAA 23).
MVAA 14
Single element relay with
electrical reset contacts.
MVAA 15
Single element relay with
hand and electrical reset contacts.
The contacts can be reset either
electrically or by hand.
Contacts
Contacts are made from a silver/copper alloy, shaped and
positioned to ensure very reliable, low resistance operations.
Normal duty make, break and changeover contacts and heavy duty
magnetic blow-out contacts are available in various combinations
(see tables 1. 2 and 3).
Heavy duty magnetic blow-out contacts are recommended for
breaking heavy or highly inductive DC loads. When these are fitted,
the number of contacts available may be reduced (see table 3).
Breaking capacity curves for these contacts are shown in figure 1
on next page.
Operation Indicators
Each relay element is supplied with an optional hand reset
operation indicator.
The indicator consists of a mask, which on operation drops to
expose a broad red strip positioned diagonally on a rectangular
white background.