The following rungs of ladder program will cause a user requested F1 trip if any

configured module should fail. An F1 trip will also be produced if the module type does

not match with the safety values entered in the configuration data.—] [————————————( )–

F372.4                                  F1.0—] [————————————( )–

F386.4                                  F1.1

6.1.2

Exchange Mode

The Exchange Mode LS byte contains the communications state indicator in bit 0. This is

set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0.  The

remainder of the byte is reserved and is cleared to 0.

The Exchange Mode MS byte contains the process data handshake mode as configured

by SyCon.

• Value = 1. Bus synchronous, device controlled.

• Value = 2. Buffered, device controlled.

• Value = 3. Non-consistent, uncontrolled.

• Value = 4. Buffered, host controlled (recommended).

• Value = 5. Bus synchronous, host controlled.

The recommended setting is buffered host controlled. This will have the least impact on

the controller’s scan rate.

All device controlled or uncontrolled settings should be avoided as the Fieldbus

communication will start as soon as power is applied, without waiting for the Ethernet

module (9716-4020) to initialise. The Fieldbus slaves will therefore not be under the

control of the GEM80.

Exchange Counter

This unsigned 32-bit variable contains the count of transfers between the GEM80 and

the Fieldbus module.

Presence Indication

The Fieldbus module maintains a bit array of the active devices detected on the

communications link. It is recommended that the application monitors this bit array and

takes appropriate action on loss of I/O. Word 0 bit 0 represents the master itself and

will always contain 0. Word 0 Bit 1represents the device with address 1 etc.

Presence Words 4 to 7 are not required when using DeviceNET and should be ignored.