ALSTOM

ALSTOM STI171 Speed Turbine

MUST HAVE

1. Controlled release of the communication by application program

2. Byte addresses

3. Little Endian

4. Buffered, host controlled

The Watchdog Time can be adjusted to suit your application (default 1000ms). It

should not be set to a value  lower than twice the longest GEM80-500 Ladder scan

rate.

Once configured OK to return to network overview.

7.4.2

Inserting Slaves

To do so select – INSERT then SLAVE

Use the mouse to position slave on the line representing the network cable, right click

to drop

Use ADD to select the required slave, then OK to confirm.

If you can not find a suitable slave you need to import the configuration file supplied

with the slave device. Importing these files is covered at the end of this document.

Download Configuration

The download of the completed configuration file is achieved using a TCP/IP

connection over Ethernet. For this reason the GEM80-500 TCP/IP Ethernet module

must be configured and operational.

Refer to Publication T2011EN GEM80 Ethernet Modules Technical Manual for

configuration and commissioning instructions.

The Sycon configuration tool automatically connects to the well known port number

1099. the user is not required to make a port selection. A correctly configured GEM80

500 TCP/IP Ethernet module will automatically create a port numbered 1099. It is not

necessary to supply this port value in the Ethernet module configuration.

The software scans the hardware at the specified IP Address and lists all compatible

Hilscher hardware found. You must select the target device for the configuration

download (tick the box), Pofibus is identified by type C104P-PB.

Note. SyCon supports a single connection to a module, whether using serial link or the

TCP/IP Method. In order to attach to a different module it is necessary to deselect the

current connection by removing the tick from the board selection field.