ALSTOM MAE 00-07 Wiring Board
MUST HAVE
1. Controlled release of the communication by application program
2. Byte addresses
3. Little Endian
4. Buffered, host controlled
The Watchdog Time can be adjusted to suit your application (default 1000ms). It
should not be set to a value lower than twice the longest GEM80-500 Ladder scan
rate.
Once configured OK to return to network overview.
7.4.2
Inserting Slaves
To do so select – INSERT then SLAVE
Use the mouse to position slave on the line representing the network cable, right click
to drop
Use ADD to select the required slave, then OK to confirm.
If you can not find a suitable slave you need to import the configuration file supplied
with the slave device. Importing these files is covered at the end of this document.
Download Configuration
The download of the completed configuration file is achieved using a TCP/IP
connection over Ethernet. For this reason the GEM80-500 TCP/IP Ethernet module
must be configured and operational.
Refer to Publication T2011EN GEM80 Ethernet Modules Technical Manual for
configuration and commissioning instructions.
The Sycon configuration tool automatically connects to the well known port number
1099. the user is not required to make a port selection. A correctly configured GEM80
500 TCP/IP Ethernet module will automatically create a port numbered 1099. It is not
necessary to supply this port value in the Ethernet module configuration.
The software scans the hardware at the specified IP Address and lists all compatible
Hilscher hardware found. You must select the target device for the configuration
download (tick the box), Pofibus is identified by type C104P-PB.
Note. SyCon supports a single connection to a module, whether using serial link or the
TCP/IP Method. In order to attach to a different module it is necessary to deselect the
current connection by removing the tick from the board selection field.