Module Identification
A rotary switch located on the fieldbus module PCB achieves module identification. A
maximum of two fieldbus modules can be installed into a GEM80-500. each identified
in the system by reserved rotary switch position 2 or 3.
The GEM80-500 Fieldbus driver will find the module with the lowest switch position
and use the configuration parameters from Pn to configure this module, this is referred
to as Module #1. The next module if fitted will use parameters from Pn+16. this
referred to as Module #2 (see section 5.2).
If a single Fieldbus module is fitted, the rotary switch must be set to position 2 (Module
#1). If two modules are fitted, one rotary switch must be set to positions 2 (Module
#1) and the other to position 3 (Module #2).
If a module is removed, ensure that the remaining module’s rotary switch is set to
position 2 and that the configuration data starting at Pn are suitable for the application.
N.B. If two modules are fitted, setting the rotary switch to the same position will cause
malfunction of both modules. Selecting any position other than 2 or 3 will cause
malfunction of the host processor.
Introduction
CAUTION
The inclusion and configuration of one or more FIELDBUS modules grants read
and write access to GEM80 data tables. It is the user’s responsibility to ensure
that adequate safeguards are used to prevent dangerous situations arising.
Module Configuration Parameters
An Advanced GEM80 Programmer (or equivalent) must be used to supply the module
configuration parameters. These parameters must be entered into the P-table of the
host GEM80 Controller by the user before the module can be used. The GEMLAN-T
Module accesses these parameters on behalf of the Fieldbus module(s) after
completion of its boot procedure. The GEMLAN-T Module takes approximately one
minute to complete its boot procedure.
Note:
If the parameters are subsequently altered, they will be recognised and
validated by the GEMLAN-T Module following a recompilation. During
the validation, Fieldbus communication is halted. If the validation
should fail, the communication remains halted.
Remember that P-table entries above P149 will only exist if specifically
declared in the user program.
For the GEMLAN-T module to access the configuration data successfully, a value must
be written into P74. This value acts as a pointer to the P-table location containing the
configuration parameters for Fieldbus module #1. Fieldbus module #2 parameters
follow those of module #1 in the P-table.
E.G. if P74 contains a value of 300. the configuration parameters start at P300.
Inserting a value of 0 into P74 renders inactive all Fieldbus modules of the host
controller.
A detailed description of each configuration parameter is provided in the following
paragraphs. Table 5-1 provides a reference table. Table 5-2 is an example of the use
of the P-tables.