Foxboro FBM204 Input Interface Module
Electronics Housing and Housing Covers
Housing has two compartments to separate the
electronics from the field connections. The housing
and covers are made from low copper (0.6%
maximum) die-cast aluminum alloy with an epoxy
finish, or from 316 ss. Buna-N O-ring seals are used
to seal the threaded housing covers, housing neck,
and terminal block.
| PROCESSOR | 958481320100 350211080090 |
| PROCESSOR | 958481320201 350211080460 |
| PROCESSOR | 958481321200 350211080320 |
| PROCESSOR | 958481321210 350211080320 |
| PROCESSOR | 958481321220 350211080320 |
| PROCESSOR | 958481321220 PD208 |
| PRO-FACE | PL5901-T42-24V |
| PROFIBUS | PB3-VME-1-E V1.2.2 |
| PROMESS | 850040060P |
| PROSOFT | 1452-25M |
| PROSOFT | 1454-9F |
| PROSOFT | 4301-MBP-DFCM |
| PROSOFT | 5201-MNET-MCM-WEB |
| PROSOFT | 5202-DFNT-MCM4 |
| PROSOFT | 5301-MBP-DH485 |
| PROSOFT | 5302-MBP-MCM4 |
Electrical Terminations
Field wires enter through 1/2 NPT, PG 13.5. or M20
threaded entrances, as specified, on either side of
the electronics housing. Wires terminate under
screw terminals and washers on terminal block in
the field terminal compartment as shown in Figure .
Unused threaded field wire entrance is plugged to
insure moisture and RFI/EMI protection.
Three- or Four-Wire Connections
Transmitter is supplied with a 4-wire terminal block,
with the two negative terminals connected internally.
This means that the transmitter can be wired with
either three wires for wiring economy, or four wires
for maximum accuracy. For relatively short wiring
runs having low resistance, 3-wire connections can
be used to minimize wiring costs. However, a voltage
drop in the common lead carrying the power supply
current will cause an error in the 1 to 5 V dc signal.
For wiring runs with high resistance due to long
lengths (or other reasons), or for maximum
accuracy, a 4-wire connection may be used to
provide input-output isolation. With 4-wire
configurations, voltage drop in the power supply loop
will have minimal effect on measurement.
Configuration and Calibration Data, and
Electronic Upgradeability
All factory characterization data, and user
configuration and calibration data are stored in the
sensor. This means that the electronics module may
be replaced, with one of like type, without the need
for reconfiguration or recalibration. Although module
replacement can affect accuracy up to 0.20% of
span, this error can be removed by an mA trim
without application of pressure.
Changing module types (from one protocol to
another) may require reconfiguration and
recalibration, as well as a different terminal block,
but all factory characterization data is retained.
Optional External Zero Adjustment
An external pushbutton (Figure 3) mechanism is
isolated from the electronics compartment and
magnetically activates an internal reed switch
through the housing. This eliminates a potential leak
path for moisture or contaminants to get into the
electronics compartment. This zero adjustment can
be disabled by a configuration selection.
Optional Transmitter Mounting Bracket Sets
Numerous mounting bracket set options are offered
to accommodate almost any mounting configuration
required. See “DIMENSIONS – NOMINAL” on
page 36.
Optional Custom Configuration (Option -C2)
For the transmitter to be custom configured by the
factory, the user must fill out a data form. If this
option is not selected, a standard default
configuration will be provided; for example: