Foxboro P0500RY Termination Cable Assembly
Adjustable Damping
Transmitter response time is normally 0.75 s, or the
electronically adjustable setting of 0 (none), 2. 4. or
8 seconds, whichever is greater, for a 90% recovery
from an 80% input step as defined in ANSI/ISA
S51.1. (For 63.2% recovery, 0.50 s with sensors B to
F, and 0.60 s for sensor A.)
Switching and Indirect Lightning Transients
Transmitter withstands transient surges to 2000 V
common mode or 1000 V normal mode without
permanent damage. Output shift is less than 1.0%.
(Per ANSI/IEEE C62.41-1980 and IEC Std. 61000-4-5.)
European Union Directives
Complies with Electromagnetic Compatibility
Requirements of European EMC Directive
2004/108/EC by conforming to the following EN
and IEC Standards: EN 61326-1. and
IEC 61000-4-2 through 61000-4-6.
Complies with NAMUR NE 21 Interference
Immunity Requirement, and NAMUR NE 43
overrange and underrange annunciations.
Conforms to Applicable European Union
Directives (“CE” Logo marked on product).
RFI Effect
Output error is less than 0.1% of calibrated span for
frequencies from 27 to 1000 MHz and field intensity
of 30 V/m when transmitter is properly installed,
shielded cable in conduit, grounding, and housing
covers in place. (Per IEC Std. 61000-4-3.)
Electronics Module
Printed wiring assemblies are conformally coated for
moisture and dust protection.
Minimum Allowable Absolute Pressure vs.
Transmitter Temperature
WITH SILICONE FILL FLUID
Full vacuum: up to 121°C (250°F)
WITH INERT FILL FLUID (see Figure 1)
Figure 1. Minimum Allowable
Absolute Pressure vs. Transmitter Temperature,
Inert FC-43. 2.6 cSt at 25°C (77°F)
TEMPERATURE, ˚C-30
ABSOLUTE PRESSURE, mmHg
120
0-25 50 100 150 200 250
TEMPERATURE, ˚F
Ease of Installation
Rotatable Topworks
allows transmitter installation in
tight places, allows indicator to be positioned in
preferred direction, and eases field retrofit.
Two Conduit Entrances
offer a choice of entry
positions for ease of installation and self-draining of
condensation regardless of mounting position and
topworks rotation.
Wiring Guides and Terminations
provide ease of
wire entry and support, plenty of space to work and
store excess wire, and large, rugged screw terminals
for easy wire termination.
Environmental Protection
The enclosure has the dusttight and weatherproof
rating of IP66 as defined by IEC 60529. and
provides the environmental and corrosion resistant
protection rating of NEMA 4X