Eaton

Eaton, Moeller, Easy MFD-CP8-NT

Eaton, Moeller, Easy MFD-CP8-NT

DATASHEET – MFD-CP8-NT

Central processing unit/power supply unit, 24 V DC, expandable, with

easyNet, program and screen memory

Delivery program

Product range  Multi-function-display MFD-Titan

Basic function  Power supply unit/CPU modules

Subrange  CPU modules

Supply voltage  24 V DC

easyNet/easyLink  mit easyNet

Description  can be combined with display/operating unit MFD-80-.. and I/O module

Expandable: Digital/analog inputs/outputs and AS-Interface, PROFIBUS-DP,

CANopen®, DeviceNet bus systems

Bussystem easyNet optional on board

Program and screen memory

Delivery with user program possible with MFD-COMBINATION product (Article no.

201801)

Description  Program and screen memory, with easyNet

Connection type  screw terminal

Degree of Protection  IP20

Technical data

General

Standards  EN 61000-6-1/-2/-3/-4. IEC 60068-2-6. IEC 60068-2-27

Dimensions (W x H x D) mm 107.5 x 90 x 30

Weight kg 0.145

Mounting  Fitted on the fixing shaft of the display or on top-hat rail according to IEC/EN 60715.

35 mm deep (without display)

Terminal capacities

Solid mm2 0.2⁄4 (AWG 24 – 12)

Flexible with ferrule mm2 0.2⁄2.5 (AWG 24 – 12)

Standard screwdriver mm 3.5 x 0.6

Climatic environmental conditions

Operating ambient temperature °C-25 to 55. cold as per IEC 60068-2-1. heat as per IEC 60068-2-2

Condensation  Take appropriate measures to prevent condensation

Storage °C- 40 – 70

Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 – 95

Air pressure (operation) hPa 795 – 1080

Ambient conditions, mechanical

Protection type (IEC/EN 60529. EN50178. VBG 4)  IP20

Vibrations (IEC/EN 60068-2-6) Hz

Constant amplitude 0.15 mm Hz 10 – 57

Constant acceleration 2 g Hz 57 – 150

Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms Impacts 18

Drop to IEC/EN 60068-2-31 Drop height mm 50

Free fall, packaged (IEC/EN 60068-2-32) m 1

Mounting position  Vertical or horizontal

Electromagnetic compatibility (EMC)

Electrostatic discharge (IEC/EN 61000-4-2. Level 3. ESD) kV

Air discharge kV 8

Contact discharge kV 6

Electromagnetic fields (RFI) to IEC EN 61000-4-3 V/m 10

Radio interference suppression  EN 55011 Class B, EN 55022 Class B

Burst Impulse (IEC/EN 61000-4-4. Level 3)

Supply cable kV 2

Signal lines kV 2

Power pulses (surge) (IEC/EN 61000-4-5) kV 2 (supply cables, symmetrical)

power pulses (surge) (IEC/EN 61000-4-5. level 2) kV 2 (supply cables symmetrical, MFD-AC-CP8..)

Immunity to line-conducted interference to (IEC/EN 61000-4-6) V 10

Insulation resistance

Clearance in air and creepage distances  EN 50178. UL 508. CSA C22.2. No. 142

Insulation resistance  EN 50178

Back-up of real-time clock

Back-up of real-time clock

① Backup time (hours) with fully charged double layer capacitor

② Service life (years)

Accuracy of the real-time clock s/day Normally ±5 s/day (±0.5 h⁄year)

Repetition accuracy of timing relays

Accuracy of timing relays (of values) % ± 0.02

Resolution

Range “S” ms 5

Range “M:S” s 1

Range “H:M” min 1

Retentive memory

Write cycles of the retentive memory  1010 (read/write cycles)

Power supply

Rated operational voltage Ue V 24 DC (-15⁄+20 %)

Admissible range V DC 20.4 – 28.8

Residual ripple % ≦ 5

Input current

at 24 V DC mA Normally 200

Voltage dips ms 10

Power loss

Heat dissipation at 24 V DC W 3.4

Note on heat dissipation  Current consumption at 24 V DC

Network easyNet

Stations Number max. 8

Data transfer rate/distance  1000 kBit/s, 6 m

500 Kbit/s, 25 m

250 Kbit/s, 40 m

125 kBit/s, 125 m

50 Kbit/s, 300 m

20 Kbit/s, 700 m

10 Kbit/s, 1000 m

Distance m 5

Potential isolation

From power supply  yes

From the inputs  yes

From the outputs  yes

to PC interface, memory card, easyNet, easyLink  yes

Bus termination (first and last station)  yes

Connection technique  RJ45. 8-pole

Design verification as per IEC/EN 61439

Technical data for design verification

Rated operational current for specified heat dissipation In A 0

Heat dissipation per pole, current-dependent Pvid W 0

Equipment heat dissipation, current-dependent Pvid W 0

Static heat dissipation, non-current-dependent Pvs W 3.4

Heat dissipation capacity Pdiss W 0

Operating ambient temperature min. °C-25