TRICONEX 9761-210 – Generic module
Termination Panels with Interposing Relays
Termination panels with interposing relays can be used with most digital output modules and
are recommended for these applications:
• Load currents greater than 2 amps
• Field voltages greater than 115 VAC
• Voltage-level conversions
• Motor-starter circuit compatibility
Interposing relay panels are available in these configurations:
• 16-point c
ommoned
• 16-point non-commoned
The digital outputs of the interposing relays are not fault-tolerant. However, each relay
provides an auxiliary contact that can be fed into a digital input to send a loopback signal to the
control program. A user-written loopback check in the control program can ensure that the relay
has achieved its commanded state. The loopback cable must be ordered separately.
Each interposing relay panel provides the capability to common power and return through a
factory-mounted bus-bar arrangement.
Each interposing relay panel consists of:
• A 7 in x 19 in (36 cm x 48 cm) rack-mountable panel with terminals for 16 digital
outputs and 16 digital inputs.
• Two ELCO connectors mounted on the panel for connecting to digital input modules
using digital input cables 9141-010. 9142-010. or 9143-010.
• An EIA standard RS-310-C plate on which the termination panel is mounted.
• A digital output module and a cable compatible with the selected coil voltage.
Bypass Panel for Digital Inputs
| Rolls-Royce | R02TCN-EOL3-00 |
| ABB | 3BHE014023R0101 UFC789AE101 |
| GE | MIVII1000E00HI00 |
| GE | MIFIIPA55E20HI00 |
| GE | IS220PAOCH1BE |
| GE | Is220Ydias1A |
| GE | Is220Pd0Ah1B |
| GE | IS220YDOAS1A |
| ABB | DSAO120 5FSE707630-71 |
| Rolls-Royce | 98H010A00001 |
| moog | G771K202 |
| GE | IS420UCSBH4A Rev.I |
| GE | IS420UCSBH1A Rev.H |
| ABB | EL3020 3.345558.2 0241398794/0300 Magnos 206 O2 98-100% |
| ABB | EL3020 3.346806.2 0241398794/1500 Caldos 27 Ar 0-100% |
| ABB | AX410/50001 |
| Foxboro | FBM217 |
| Foxboro | FBM201 P0914SQ |
| Foxboro | FBM237 P0914XS |
| Foxboro | FBM203 RH914SV |
| Foxboro | FBM201TA P0916AA |
Bypass termination panels can be used to connect digital inputs using a bank of 32 pre-wired
switches. Bypass panels have a master keyswitch and terminals for redundant +24 VDC power
sources. Each input point contains an ON status indicator and can be energized only if the
master keyswitch is ON and the corresponding point switch is ON. Each point has a location for
a user-definable label.
Each bypass termination panel comes with one or two 10-foot (3-meter) cables for connecting
the termination panel to a Tricon backplane
Termination Panel with RTD/TC/AI Input Signal Conditioning
Termination panels which use industry-standard analog signal conditioners provide a flexible,
user-configurable interface to resistive thermal devices (RTDs), thermocouples, and 4-20 mA
transmitters. Each termination panel supports 16 points and each analog module can support
up to 2 panels. These termination panels are compatible with any signal conditioners in the 1 to
5 volt output range. For example, the 7B series of signal conditioners from Analog Devices™ are
known to work well.
Termination Panel 9251-210 for Digital Output Module 3603B
The special 16-point non-commoned digital output termination panel 9251-210 is required for
use with the 16-point non-commoned digital output module 3603B.
Termination Panel 9863-710 for Analog Output Module 3806E
The special analog output termination panel 9863-710. with buffered loopback signals, is
available for use with the high-current analog output module 3806E