Triconex

TRICONEX 3604E – Generic module

Termination Panels with Interposing Relays

Termination panels with interposing relays can be used with most digital output modules and

are recommended for these applications:

• Load currents greater than 2 amps

• Field voltages greater than 115 VAC

• Voltage-level conversions

• Motor-starter circuit compatibility

Interposing relay panels are available in these configurations:

• 16-point c

ommoned

• 16-point non-commoned

The digital outputs of the interposing relays are not fault-tolerant. However, each relay

provides an auxiliary contact that can be fed into a digital input to send a loopback signal to the

control program. A user-written loopback check in the control program can ensure that the relay

has achieved its commanded state. The loopback cable must be ordered separately.

Each interposing relay panel provides the capability to common power and return through a

factory-mounted bus-bar arrangement.

Each interposing relay panel consists of:

• A 7 in x 19 in (36 cm x 48 cm) rack-mountable panel with terminals for 16 digital

outputs and 16 digital inputs.

• Two ELCO connectors mounted on the panel for connecting to digital input modules

using digital input cables 9141-010. 9142-010. or 9143-010.

• An EIA standard RS-310-C plate on which the termination panel is mounted.

• A digital output module and a cable compatible with the selected coil voltage.

Bypass Panel for Digital Inputs

Bypass termination panels can be used to connect digital inputs using a bank of 32 pre-wired

switches. Bypass panels have a master keyswitch and terminals for redundant +24 VDC power

sources. Each input point contains an ON status indicator and can be energized only if the

master keyswitch is ON and the corresponding point switch is ON. Each point has a location for

a user-definable label.

ABB AX410/50001
Foxboro FBM217
Foxboro FBM201 P0914SQ
Foxboro FBM237 P0914XS
Foxboro FBM203 RH914SV
Foxboro FBM201TA P0916AA
Foxboro FBM237TA P0916CC
Foxboro FBM203TA PO916AE
Foxboro P0916DE
ABB 3BHE057901R0101 PCD235C101
Triconex 3704E
Triconex 3504E
Triconex 3504E
EMERSON 1X00781H01L
EMERSON PR6423 009-041+CON 041/913-030
KONSGBERG RCU500
KONSGBERG RMP400
KONSGBERG RDIOR400
Cutler Hammer 1775K PMPP1700
MOORE INDUSTRIES MDS/PRG/10-30DC/-MAO

Each bypass termination panel comes with one or two 10-foot (3-meter) cables for connecting

the termination panel to a Tricon backplane

Termination Panel with RTD/TC/AI Input Signal Conditioning

Termination panels which use industry-standard analog signal conditioners provide a flexible,

user-configurable interface to resistive thermal devices (RTDs), thermocouples, and 4-20 mA

transmitters. Each termination panel supports 16 points and each analog module can support

up to 2 panels. These termination panels are compatible with any signal conditioners in the 1 to

5 volt output range. For example, the 7B series of signal conditioners from Analog Devices™ are

known to work well.

Termination Panel 9251-210 for Digital Output Module 3603B

The special 16-point non-commoned digital output termination panel 9251-210 is required for

use with the 16-point non-commoned digital output module 3603B.

Termination Panel 9863-710 for Analog Output Module 3806E

The special analog output termination panel 9863-710. with buffered loopback signals, is

available for use with the high-current analog output module 3806E

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注