SAUTER AXM 217S: Motorised actuator for unit valves with positioner

AXM 217S: Motorised actuator for unit valves with positioner

How energy efficiency is improved

Automatic adaptation to valve and intelligent cut-off for maximum energy efficiency

Features

• Stepping motor with electronic activation and cut-out

• Attached to valve with M30 × 1.5 thread

• Version with direction of operation 1 (direct acting) or 2 (reverse acting), adjustable

• Adjustable valve strokes

• Automatic stroke adjustment (AXM217SF404)

•Maintenance-free gear unit

• Suitable for retrofitting existing installations using the appropriate adapters

• Status and diagnostic indicator via integrated bi-colour LED

• Fitting position vertically upright to horizontal, not suspended

Technical data

Power supply

Power supply 24 V~/=, ±15%, 50…60 Hz

Power consumption 2.5 VA / 1.5 W

Parameters1)

Direction of operation 1 or 2 (adjustable)

Nominal stroke 3.2 mm, 4.3 mm, 5.5 mm (adjustable)

Automatic stroke adjustment (F404)

Running time 8 s/mm

Sound pressure level < 30 dB(A)

Control signal 0(2)…10 V; 5…10 V; 0…5 V

Ri > 100 kΩ;

0(4)…20 mA

Ri = 500 Ω

Ambient conditions

Admissible ambient temperature 0…50 °C, no condensation

Max. operating temperature at valve 95 °C

Storage and transport temperature–20…65 °C

Admissible ambient humidity < 75% rh

Construction

Weight 0.15 kg

Housing Two-part, light grey (RAL 7035)

Housing material Plastic

Thread Nickel-plated brass M30 × 1.5

Power cable 1.50 m long, 3 × 0.5 mm², light grey,

pluggable

3.0 m long, halogen-free (F404)

Standards and directives

Type of protection IP43 (EN 60529)

Protection class III (IEC 60730)

CE conformity according to EMC Directive 2014/30/EU 61000-6-1. 61000-6-2. 61000-6-3 and

EN 61000-6-4

Overview of types

55.022

Type

Features

AXM217SF402 Motorised actuator for unit valves with position

er

Actuating power

120 N

AXM217SF404 Motorised actuator for unit valves with position

er and automatic stroke adjustment

A AXM217SF402: Actuating power min. 100 N, max. 150 N

Accessories

160 N

Type

0550603009

0550603010

0550603011

0550603012

0371235001

0550393002

0550393003

0371356001

0371361001

0371363001

Description

Cable: 24 V, PVC, pluggable, 3 m long

Cable: 24 V, PVC, pluggable, 7 m long

Cable: 24 V, halogen-free, pluggable, 3 m long

Cable: 24 V, halogen-free, pluggable, 7 m long

Adaptor for fitting to Oventrop valves (M30 × 1)

Adapter for fitting to Danfoss valves, type RAVL, 26 mm

Adapter for fitting to Danfoss valves, type RAV, 34 mm

Adaptor for fitting to Beulco or Tobler underfloor-heating distributors (M30 × 1)

Adapter for fitting to Herz valves, type Herz-TS’90 (M28 × 1.5)

Adapter for fitting to Tour & Andersson valves, type TA/RVT (M28 × 1.5)

0550393004

Adapter for fitting to Danfoss valves, type RA 2000. 22 mm

Description of operation

Auto-calibration: During commissioning (with valve fitted), the spindle of the actuator moves com

pletely to the bottom (zero point). Then the spindle moves to the position that corresponds to the con

trol signal. Confirmation of the end position: When the actuator has been in its start or end position for

a lengthy period, every 2 hours the control signal is activated for around 60 seconds. This automati

cally recalibrates the actuator. The motor positions the valve and cuts out as soon as the stroke posi

tion matches the controller signal. The LED indicator lights up if power is applied and flashes as long

as the motor is running.

Direction of operation 1:

• As the positioning signal increases, the actuator spindle moves out and the VUL, VUT, VCL, VDL 2

way valves and the BUL 3-way valve (control passage) close. With the BXL 3-way valve, the control

passage opens.

Direction of operation 2:

• As the positioning signal increases, the actuator spindle moves in and the VUL, VUT, VCL, VDL 2

way valves and the BUL 3-way valve (control passage) open. With the BXL 3-way valve, the control

passage closes.

After the cap on the cover is removed, the following settings can be made using jumpers:

• Setting of the input signal. This can be set to either 0…10 V or 5.2…10 V or 0…4.8 V.

• Direction of operation 1 or 2 can be selected; the factory setting is direction of operation 2 (RA).

Put the cap back on after making the settings