Shinkawa

SHINKAWA VM-705B 18-CHANNEL TEMPERATURE   MONITOR MODULE

VM-705B 18-CHANNEL TEMPERATURE
MONITOR MODULE
Input points : 18 points
Input impedance : more than 1MΩ (Thermo-couple)
Input transducer : Thermo-couple (Type E, Type J, Type K, Type T)
100Ω 3wireRTD (R100/R0 =1.3851)
100Ω 4wireRTD (R100/R0 =1.3851)
MONITOR RANGE
Thermo-couple (Type E) :  -200°C to 990°C
Thermo-couple (Type J) :  -140°C to 1190°C
Thermo-couple (Type K) :  -200°C to 1362°C
Thermo-couple (Type T) :  -200°C to 390°C
100Ω RTD :  -200°C to 850°C
MEASURE LIMIT
Thermo-couple (Type E) :  -270°C to 1000°C
Thermo-couple (Type J) :  -210°C to 1200°C
Thermo-couple (Type K) :  -270°C to 1372°C
Thermo-couple (Type T) :  -270°C to 400°C
100Ω RTD :  -200°C to 850°C
COLD JUNCTION COMPENSATION SENSOR (RJC)
Attachment :  No installation required (Built-in chip)
MEASURE
Mode : Direct, Composite, Differential
Direct         : Direct temperature
Composite    : Average temperature of the selected input channel
(If the number of the selected input channel is one,
the value of Composite is the same as Direct.)
Differential    : Temperature difference obtained by subtracting
Composite from Direct
Note)
・Composite and Differential can be enabled/disabled by the setting.
・Input channels to be selected for Composite can be set by the channel,
but they must be from the same slot.
・To the recorder output and the output via Modbus communication,
users can assign one of the modes above.
・ When this monitor is used for intrinsically safe explosion proof construction, the
OK alarm set point may fall within the range, depending on the input
transducer and the specified monitoring range.

OUTPUT
Indicator : ACTIVE LED (Green)
On : Normal
Flash : The 18-Channel Temperature Input
Module is not installed properly
OK LED (Green)
On : Normal
Flash : When OK alarm occurs
(When an OK alarm is output in any of
channels 1 through 18.)
Burnout function : Down scale Zero(Zero value)
Up scale +110% or more
Contact output : None
※ By using the VM-721B or VM-722B Relay Module,
contact signals output from the relay can be output from the
contact output terminal block on the instrument rack.
ALARM
Alarm set point : Up to 4 points for each channel, each mode, from
0 to 100% of monitor range, field changeable.
H-DANGER, H-ALERT, L-ALERT, L-DANGER

Alarm set accuracy : ± (0.2% of F.S. +1digit) or less at 25°C
Alarm set repeatability : ±1digit or less at 25°C
Alarm delay time : 0 to 99sec (0.1 sec step, field changeable)
Alarm reset : AUTO-RESET or SELF-HOLD field changeable.

BYPASS
First Low Alarm Bypass function : Suppress low alarm when low alarm is
detected for the first time after turning on the
power
Danger bypass : Block off alarm output (DANGER)
Channel bypass :  Block off alarm output
(DANGER, ALERT, OK and indication values)
ENVIRONMENTAL CONDITION
Operating temperature : 0 to +65°C
Storage temperature : -30 to +85°C
Relative humidity : 20 to 95%RH (non-condensing)

18-CHANNEL TEMPERATURE MONITOR MODULE
POWER CONSUMPTION
Module  : Less than 15W
MATERIAL AND FINISH
Face plate : ABS (Black)
Sheet : Polyester tough top (Gray)
Base plate : Alminium alloy (Silver)
MASS
Body : Max. 1.0kg (2.2lb)

18-CHANNEL TEMPERATURE INPUT MODULE
POWER CONSUMPTION
Module  : Less than 15W
MATERIAL AND FINISH
Base plate : ZAM (Silver)
MASS
Body : Max. 1.0kg (2.2lb)

ACCESSORY SPECIFICATION CODE / IDENTIFIED BY TB3

Code Accessory Quantity
(Part Code)
/TB3 Transducer input terminal plug (15pin)
FMC-1,5/15-ST-3,5-RF (PHOENIX CONTACT)
6pieces *1
(7072NAW)

Note)*1 When individually ordering specify the parts code,it is require to
arrange for a necessary amount.

INPUT
Input points : 18 points
Input transducer : 100Ω 3-wire RTD (R100/R0=1.3851)
(non-intrinsic safety)
Monitor range : 0 to 200°C
MEASURE
Mode : Direct only

ALARM
Alarm(Direct)
H-DANGER set point : 160°C
H-ALERT set point : 120°C
L-ALERT set point : None
L-DANGER set point : None
Alarm delay time : 3sec (DANGER, ALERT)
Alarm reset : AUTO-RESET

OTHERS
Initial low alarm bypass : OFF
First out : OFF
Timed OK channel defeat : ON
Burnout(Direct) : Downscale 0%

Specification
Default Value
! WARNING
Some functions may not be available with old version.
For details, please refer to “infiSYS Family Improvement
Information” (6H16-011).