SHINKAWA VM-704B TEMPERATURE MONITOR MODULE

VM-704B TEMPERATURE
MONITOR MODULE
INPUT
Input points : 6 points
Input impedance : more than 1MΩ (Thermo-couple)
Input trancdusor : Thermo-couple (Type E, Type J, Type K, Type T)
100Ω 3wireRTD (R100/R0 =1.3851)
100Ω 4wireRTD (R100/R0 =1.3851)
MONITOR RANGE
Thermo-couple (Type E) :  -200°C to 990°C
Thermo-couple (Type J) :  -140°C to 1190°C
Thermo-couple (Type K) :  -200°C to 1362°C
Thermo-couple (Type T) :  -200°C to 390°C
100Ω RTD :  -200°C to 850°C
MEASURE LIMIT
Thermo-couple (Type E) :  -270°C to 1000°C
Thermo-couple (Type J) :  -210°C to 1200°C
Thermo-couple (Type K) :  -270°C to 1372°C
Thermo-couple (Type T) :  -270°C to 400°C
100Ω RTD :  -200°C to 850°C
COLD JUNCTION COMPENSATION SENSOR(RJC)
Attachment :  To monitor output connector (1piece/module)
Compensation accuracy :  ±1°C at 25°C

Emerson 1C31227G01
Emerson 1C31219G01
Motorola FLN3566A
BHEL PDP601B
SAUTER AVM234SF132
Allied Telesyn AT-800S/24
GE IS200ESYSH3A
ABB 3BHE004468R0021 GDC780BE21
ABB V28451A-1312131
SEL SEL-700BT
ABB UC D240 / 3BHE022287R0101
ABB UNS2980C-Z HIEE205019R0004
A-B 1797-PS2E2
HONEYWELL FC-RUSIO-3224
Bently 3500/32M-01-01-CN
Bently 330903-04-15-05-02-00
Bently 3500/32M-01-CN
Bently 3500/32M-01-01-CN

MEASURE
Mode : Direct, Composite, Differential
Direct         : Direct temperature
Composite    : Average temperature of the selected input channel
(If the number of the selected input channel is one,
the value of Composite is the same as Direct.)
Differential    : Temperature difference obtained by subtracting
Composite from Direct
Note)
・Composite and Differential can be enabled/disabled by the setting.
・Input channels to be selected for Composite can be set by the channel,
but they must be from the same slot.
・To the recorder output and the output via Modbus communication,
users can assign one of the modes above.
・When this monitor is used for intrinsically safe explosion proof construction, the
OK alarm set point may fall within the range, depending on the input
transducer and the specified monitoring range.

OUTPUT
Indicator : OK LED (Green)
When channel is normal : ON, When alarming : Flashing
Recorder output : Voltage or current output proportional to measurement
value.
Measurement value of each channel can be assigned to
any output channel of its own module.
Number of output points : 6points
Output range   : 1 to 5V, 4 to 20mA
0 to 5V, 0 to 10V
I/O conversion accuracy:±(1% of F.S.+1°C) at 25°C
± (2% of F.S. +1°C) at 0°C to 65°C
(Monitor range: 200°C or more)
Max. load resistance : 600Ω (current mode)
Output impedance : Approx. 500Ω (voltage mode)
Insulation resistance : 10MΩ at 100VDC
Burnout function : Down scale 0%
Down scale 0mA / 0mV
Up scale +110% or more
Contact output : Number of relay: 6 points (logic changeable)
Contact type: Dry contact (SPDT)
Energization method : Normally de-energized or Normally
energized field changeable
Contact capacity: 250VAC/5A, 30VDC/5A

ALARM
Alarm set point : Up to 4 points for each channel, each mode, from
0 to 100% of monitor range, field changeable.
H-DANGER, H-ALERT, L-ALERT, L-DANGER

Alarm set accuracy : ± (0.2% of F.S. +1digit) or less at 25°C
Alarm set repeatability : ±1digit or less at 25°C
Alarm delay time : 0 to 99sec (0.1 sec step, field changeable)
Alarm reset : AUTO-RESET or SELF-HOLD field changeable.
Alarm bypass function : Block off alarm output (DANGER)