Eaton

Eaton XN-322-8AI-I Analog input modules

eneral specifications
Product Name
Eaton XN-322 Input module
Catalog Number
179288
Model Code
XN-322-8AI-I
EAN
7640130098381
Product Length/Depth
104.2 mm
Product Height
16.8 mm
Product Width
80.3 mm
Product Weight
0.056 kg
Certifications
UL File No.: E135462
cULus
CE
EN 61131-2
EN 61000-6-2
EN 61000-6-4
UL508
CSA-C22.2 No. 142-M
Catalog Notes
The max. heat dissipation is specified as the maximum power produced inside the device’s housing.
Ambient conditions, mechanical
Height of fall (IEC/EN 60068-2-32) – max
1 m
Mounting position
Horizontal
Shock resistance
15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts
Vibration resistance
5 – 8.4 / 8.4 -150 Hz, 3,5 mm / 1 g
Climatic environmental conditions
Air pressure
795 – 1080 hPa (operation)
Ambient operating temperature – max
60 °C
Ambient storage temperature – max
85 °C
Ambient operating temperature – min
0 °C
Ambient storage temperature – min
-20 °C
Climatic proofing
Dry heat to IEC 60068-2-2
Damp heat, constant, to IEC 60068-2-3
Environmental conditions
Condensation: prevent with appropriate measures
Relative humidity
0 – 95 % (non-condensing)
Communication
Connection type
2 conductors, Current measurement
Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction
Protocol
Other bus systems
Design verification
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard’s requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard’s requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard’s requirements.
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of assemblies
Meets the product standard’s requirements.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
Equipment heat dissipation, current-dependent Pvid
0 W
Heat dissipation capacity Pdiss
0 W
Heat dissipation per pole, current-dependent Pvid
0.97 W
Rated operational current for specified heat dissipation (In)
0 A
Static heat dissipation, non-current-dependent Pvs
1.485 W
Electrical rating
Rated operational voltage
160 V (terminations)
Supply voltage at DC – max
30 VDC
Supply voltage at DC – min
18 VDC
Electro magnetic compatibility
Air discharge
8 kV
Burst impulse
2 kV, Supply cable
1 kV, Signal cable
Contact discharge
4 kV
Electromagnetic fields
10 V/m at 0.08 – 1.0 GHz (according to IEC EN 61000-4-3)
1 V/m at 2 – 2.7 GHz (according to IEC EN 61000-4-3)
3 V/m at 1.4 – 2 GHz (according to IEC EN 61000-4-3)
Emitted interference
40 dB (at 30 – 230 MHz, Class A, radiated, high frequency)
47 dB (at 230 – 1000 MHz, Class A, radiated, high frequency)
Radiated RFI
10 V
Surge rating
1 kV, Signal cable, unbalanced, EMC
0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC
Voltage dips
Voltage dips: 10 ms/Voltage fluctuations: Yes
Features & functions
Current measurement
50 Ω typ., input resistance
0 – 20 mA
4 – 20 mA
Electric connection type
Plug-in connection
Features
Fieldbus connection over separate bus coupler possible
Analog outputs configurable
Input, current
Analog inputs configurable
Input signal, configurable
Fieldbus connection over separate bus coupler possible
Fitted with:
Parameterizable Software input filter
1 kHz, third-order low-pass input filter
Value representation
SIGNED16, Current measurement
General information
Current consumption
30 mA (typ.), for +24 V, Power supply – Input
50 mA (typ.), for +5 V power