Eaton XN-322-10AI-TEKT Analog input module
The MP-3000 Motor Protection Relay serves as a direct replacement
for the prior generation Westinghouse® or Cutler-Hammer IQ 1000 II.
The cutout and mounting are compatible. The relay terminal configu
ration and wiring connections are similar.
MP-3000 features and Enhancements
The MP-3000 Motor Protection Relay incorporates the field proven
motor thermal models and sequence component measurement
techniques that were pioneered in the IQ 1000 II relay thermal models.
The MP-3000 also adds several enhancements. Significant enhance
ments and features include:

1. Recognized to meet UL 1053 Standards for Ground Fault Protec
tion Devices.
2. Power supply operates continuously at 55% of nominal supply
voltage. It can ride through a voltage sag or loss for 30 cycles
without dropping out and taking the motor off line.
3. Optional Quick Release Drawout Case that makes removal and
replacement fast and easy.
4. New Armed/Disarmed feature for trip-free installation with Quick
Release Drawout Case.
5. User selectable trip or alarm only on relay internal failure detec
tion.
6. Real-time clock for date and time stamping of trips, alarms, and
events (Y2K compliant).
7. Expanded memory for extensive recording and logging of events,
trips, alarms, history, and motor starting current profiles.
8. Motor starting profile plot versus protection limits.
9. Easy-to-use faceplate and user interface. Settings and data are
organized into pages under six main modes. The modes are
Default (motor state), Monitor, View Setting, History, Logs, and
Program (change settings).
10. intel-i-trip Intelligent Overload Protection with adaptive trip char
acteristics based on RTD readings and motor operating history.
11. RTD diagnostics and communications error checking for addi
tional security against operation from RTD failures.
12. Mechanical Process Load Shedding feature provides overload
indication to control upstream processes, averting unnecessary
motor overload shutdown or jam trips, and maintaining process
continuity