Eaton Cutler-Hammer FP5000-00 / FP5200-00 66D2041G11

1  Product Overview

1.1  General Description

The Eaton FP-5000 Protective Relay is a multifunction panel

mounted, microprocessor-based relay, designed for both ANSI

and IEC applications (Figure 1). It is a self-contained device which

operates from either ac or dc control power and provides true

rms sensing of each phase and ground current. Only one relay is

required per 3-phase circuit. Current, voltage and operator

selectable protective functions are integral to each device.The FP

5000 is designed to protect the mains, ties or feeders at any

voltage level. It is primarily applied on medium voltage

distribution circuits up to 69 kV. The FP-5000 monitors several

primary and derived electrical parameters of the system.

1.2  Audience

The audience for this document is the Specifying or System

Engineer, the operating personnel and the troubleshooting

personnel. This document will guide the system user to apply

and program the FP-5000. The document will provide operating

information, enabling the operating user to start and trip the

breaker associated with the FP-5000. The operator can refer to

this publication regarding any operation of the FP-5000. This

document will also provide information to program the FP-5000

and use the troubleshooting features to collect and analyze

historical, trending and oscillographic data.

Referenced Documents

IMPACC Communications Standard, IL 17384.

IEEE Standard Electrical Power System Device Function

Numbers and Contact Designations, # C37.2-1996. ISBN 0-7381

0732-8 Standard IEEE Device Numbers.

FP5000-00

1.5  Commercial and Trademarks

Acrobat™

Explorer™

IMPACC™

INCOM™

IEEE™

PowerNet™

PowerPort™

Windows®

Adobe® Corporation

Microsoft® Corporation

Eaton

Eaton

Institute of Electrical and Electronic

Engineers

Eaton

Eaton

Microsoft Corporation

1.6  FP-5000 Hardware Resources and Description

The FP-5000 has four current measuring inputs, four voltage

measuring inputs, eight contact inputs, seven contact output

relays, communications and a front panel user interface.

Based upon the firmware loaded into the flash memory of the

FP-5000 and the customer settings entered manually through the

front panel or through the RS-232 port using the PowerPort

program, the microprocessor observes inputs, sets outputs and

stores data for user retrieval

The purpose of a Quick Start section is to provide a minimal

overview of what it takes to operate the FP-5000. This

perspective is useful as either providing the framework for

learning the FP-5000 more thoroughly or for actually handling a

simple application. The FP-5000 is approachable at a variety of

levels. Significant results may be obtained with basic knowledge,

yet the FP-5000 is powerful enough to handle the most difficult

and involved of applications.

Use this Guide to begin performing basic metering functions

quickly, without reviewing complete instructions provided in the

User’s Manual. To more fully understand the wide array of

features offered by your FP-5000. it is strongly recommended

that operators read the entire User’s Manual. Following initial

power-up of the FP-5000. the displayed “Meter Menu” values

may not be what is anticipated for your specific system. The unit

must first be programmed with “General Setup” information

relating to your electrical system.

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注