Your FP-5000 will either come pre-installed in a panel or as a
separate FP-5000 component assembly package including an
“Outer Chassis” assembly and an “Inner Chassis” assembly
containing the major portion of the operating electronics. Follow
Section 7 “Startup” if a review of the installation is required.
2.3 Standard Mounting
The FP-5000 is shipped with the Outer Enclosure assembled with
a backing plate between the enclosure housing box and the front
latching frame. This factory assembled outer chassis allows for
panel thickness variations, minor panel distortions and has
relaxed panel cutout tolerance requirements for easy faster panel
mounting. The panel footprint outline is equivalent to the Eaton
DT3XXX and MP3XXX drawout designs. However it differs from
most Eaton IQ style panel mounts in that:
• The panel cutout is slightly larger.
• The enclosure is mounted from the front user side of the
panel.
• Four mounting studs/nuts are used for panel mounting instead
of 10 mounting screws.
The standard panel cutout is shown in Figure 3.
Please refer to Section 6.1 for mounting details.
For IQ Panel Cutout Retrofit see Section 6.2.
Introduction to Programming
The FP-5000 can be programmed using an HMI with PowerPort™
software through the RS-232 serial port or remotely via the rear
INCOM PN using PowerNet. In addition, the FP-5000 may be
programmed directly from the front panel. We will focus on
direct programming from the front panel in this Quick Start
Section. Programming is restricted to authorized users through
password protection and through the physical restraint of a
security door which may be sealed with a lead seal
Lift the security door cover over
the Set and Test buttons on the
front panel and press the Set
pushbutton. The Set LED (at the
upper right corner of the Set
pushbutton) will illuminate and
the display will change to the
Password request Window.
Unauthorized programming is
prevented by password
protection and by means of the
security door over the Set
pushbutton, which may be
secured with the lead seal,
making apparent any
programming access. Minimal
programming will be described
in this Quick Start section. Please
refer to the complete
programming instructions in
Setting the
FP-5000. Section 5.
The Setting Mode from the Front Panel is password protected to
prevent access by unauthorized users. In order to access the
programming mode of the FP-5000 a password must be entered.
Each Password is a 4-character alphanumeric value. The FP-5000
is shipped with the password protection effectively disabled, set
to the default of ‘0000’. Entering Program Mode (or Test Mode)
with acceptance of the default password is done by pressing the
Enter button with the 4-asterisk Password display unchanged.
Each character in the Password may be modified to any of the
characters 0-9 and A-Z within program mode.