Your FP-5000 will either come pre-installed in a panel or as a

separate FP-5000 component assembly package including an

“Outer Chassis” assembly and an “Inner Chassis” assembly

containing the major portion of the operating electronics. Follow

Section 7 “Startup” if a review of the installation is required.

2.3  Standard Mounting

The FP-5000 is shipped with the Outer Enclosure assembled with

a backing plate between the enclosure housing box and the front

latching frame. This factory assembled outer chassis allows for

panel thickness variations, minor panel distortions and has

relaxed panel cutout tolerance requirements for easy faster panel

mounting. The panel footprint outline is equivalent to the Eaton

DT3XXX and MP3XXX drawout designs. However it differs from

most Eaton IQ style panel mounts in that:

• The panel cutout is slightly larger.

• The enclosure is mounted from the front user side of the

panel.

• Four mounting studs/nuts are used for panel mounting instead

of 10 mounting screws.

The standard panel cutout is shown in Figure 3.

Please refer to Section 6.1 for mounting details.

For IQ Panel Cutout Retrofit see Section 6.2.

Introduction to Programming

The FP-5000 can be programmed using an HMI with PowerPort™

software through the RS-232 serial port or remotely via the rear

INCOM PN using PowerNet. In addition, the FP-5000 may be

programmed directly from the front panel. We will focus on

direct programming from the front panel in this Quick Start

Section. Programming is restricted to authorized users through

password protection and through the physical restraint of a

security door which may be sealed with a lead seal

Lift the security door cover over

the Set and Test buttons on the

front panel and press the Set

pushbutton. The Set LED (at the

upper right corner of the Set

pushbutton) will illuminate and

the display will change to the

Password request Window.

Unauthorized programming is

prevented by password

protection and by means of the

security door over the Set

pushbutton, which may be

secured with the lead seal,

making apparent any

programming access. Minimal

programming will be described

in this Quick Start section. Please

refer to the complete

programming instructions in

Setting the

FP-5000. Section 5.

The Setting Mode from the Front Panel is password protected to

prevent access by unauthorized users. In order to access the

programming mode of the FP-5000 a password must be entered.

Each Password is a 4-character alphanumeric value. The FP-5000

is shipped with the password protection effectively disabled, set

to the default of ‘0000’. Entering Program Mode (or Test Mode)

with acceptance of the default password is done by pressing the

Enter button with the 4-asterisk Password display unchanged.

Each character in the Password may be modified to any of the

characters 0-9 and A-Z within program mode.