SHINKAWA MODEL VM-5Y1,2,3 RELAY MODULE UNIT
MODEL VM-5Y1,2,3 RELAY MODULE UNIT
Relay contact Arc suppressor Input Tropical
spec.
1 SPDT (DAN.1,DAN.2,ALE.1,ALE.2)4 points relay 0 Provided 1 CA Series,CV-86 *1
1 Not provided 2 CV-85,CV-87 *2
VK,RD,FK,MS
VC,VM-11P,VM-21P
4 Input for VM-55
1CH:VK-202A,FK-202F
2CH:CV-86,CV-88
Relay contact Arc suppressor Input Relay mode*3
(DANGER)
Relay mode*3
(ALERT)
Tropical
spec.
2 DPDT (DAN.,ALE.)2 points relay 0 Provided 1 CA Series,CV-86 *1 0 NORMALY
DE-ENERGIZED
0 NORMALY
DE-ENERGIZED
1 Not provided 2 CV-85,CV-87 *2
VK,RD,FK,MS
VC,VM-11P,VM-21P
1 NORMALY
ENERGIZED
1 NORMALY
ENERGIZED
4 Input for VM-55
1CH:VK-202A,FK-202F
2CH:CV-86,CV-88
Relay contact Arc suppressor Intput Contact method
(DANGER)
Contact method
(ALERT)
Contact method
(OK)
Tropical
spec.
3 SPDT (DAN.1,DAN.2,ALE.1,ALE.2,OK1,OK2)6 points relay 0 Provided 1 CA Series,CV-86 *1 1 NO 1 NO 1 NO
1 Not provided 2 CV-85,CV-87 *2
VK,RD,FK,MS
VC,VM-11P,VM-21P.
2 NC 2 NC 2 NC
4 Input for VM-55
1CH:VK-202A,FK-202F
2CH:CV-86, CV-88
RELAY POINTS 4 points(DANGER1,ALERT1,DANGER2,ALERT2)
2 points(DANGER,ALERT)
6 points(DANGER1,AERLT1,DANGER2,ALERT2,OK1,OK2)
POWER OUTPUT
FOR TRANSDUCER
4mA, 24VDC (input code:1) -24VDC,40mA (input code:2)
1CH : -24VDC, 40mA 2CH : 4mA, 24VDC (input code:4)
CONTACT RATING
(LOAD RESISTANCE)
250VAC,5A 30VDC,5A
OTHERS
CONTACT LIFE 100,000 or more(rated load)
PROTECTIVE
CONSTRUCTION
Plastic seal
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (+32 to +149°F REF.)
Storage temperature : -30 to +85°C(-22 to +185°F REF.)
Relative humidity : 20 to 95%RH (noncondensing)
MASS max.0.4kg (max.0.9lb REF.)
Alarm contact operation
Monitor alarm relay mode Monitor power OFF Monitor power ON
Normal state Alarm state
NO contact NORMALLY DE-ENERGIZED OPEN OPEN CLOSE
NO contact NORMALLY ENERGIZED OPEN CLOSE OPEN
NC contact NORMALLY DE-ENERGIZED CLOSE CLOSE OPEN
NC contact NORMALLY ENERGIZED CLOSE OPEN CLOSE