SHINKAWA MODEL VM-5M DUAL PATH MONITOR
MODEL VM-5M DUAL PATH MONITOR
1 0 to 20m/s2 pk J 0 to 10mm/s pk 1 0 to 20mm/s pk 1 CV-85*6 1 10Hz or less 1 10Hz or less 1 100Hz 1 100Hz
2 0 to 50m/s2 pk K 0 to 20mm/s pk 2 0 to 50mm/s pk 2 CV-86 2 20Hz 2 20Hz 2 200Hz 2 200Hz
3 0 to 100m/s2 pk L 0 to 50mm/s pk 3 0 to 100mm/s pk 3 CV-87*6 3 50Hz 3 50Hz 3 500Hz 3 500Hz
4 0 to 200m/s2 pk M 0 to 10mm/s rms
*2 4 0 to 20mm/s rms
*2 4 CA Series 4 100Hz 4 100Hz 4 1kHz 4 1kHz
5 0 to 20m/s2 rms
*2 N 0 to 20mm/s rms
*2 5 0 to 50mm/s rms
*2 5 200Hz 5 200Hz 5 2kHz 5 2kHz
6 0 to 50m/s2 rms
*2 P 0 to 50mm/s rms
*2 6 0 to 100mm/s rms
*2 6 500Hz 6 500Hz 6 5kHz 6 5kHz
7 0 to 100m/s2 rms
*2 Q 0 to 0.5in/s pk 7 0 to 1in/s pk 7 1kHz 7 1kHz 7 10kHz 7 10kHz
8 0 to 200m/s2 rms
*2 R 0 to 1in/s pk 8 0 to 2in/s pk 8 9.5Hz Seismic filter
*4 8 9.5Hz Seismic filter
*4 8 20kHz 8 20kHz
A 0 to 2g pk S 0 to 2in/s pk A 0 to 1in/s rms
*2 A 14Hz Seismic filter
*4 A 14Hz Seismic filter
*4
B 0 to 5g pk T 0 to 0.5in/s rms
*2 B 0 to 2in/s rms
*2 B 15Hz Seismic filter
*4 B 15Hz Seismic filter
*4
C 0 to 10g pk U 0 to 1in/s rms
*2 C 0 to 100m pk-pk C 40Hz(36dB/oct)
Pipe filter
*4 C 40Hz(36dB/oct)
Pipe filter
*4
D 0 to 20g pk V 0 to 2in/s rms
*2 D 0 to 200m pk-pk
E 0 to 2g rms
*2 E 0 to 500m pk-pk D 60Hz(36dB/oct)
Pipe filter
*4 D 60Hz(36dB/oct)
Pipe filter
*4
| ABB | 3BHE014023R0101 UFC789AE101 |
| GE | MIVII1000E00HI00 |
| GE | MIFIIPA55E20HI00 |
| GE | IS220PAOCH1BE |
| GE | Is220Ydias1A |
| GE | Is220Pd0Ah1B |
| GE | IS220YDOAS1A |
| ABB | DSAO120 5FSE707630-71 |
| Rolls-Royce | 98H010A00001 |
| moog | G771K202 |
| GE | IS420UCSBH4A Rev.I |
| GE | IS420UCSBH1A Rev.H |
| ABB | EL3020 3.345558.2 0241398794/0300 Magnos 206 O2 98-100% |
| ABB | EL3020 3.346806.2 0241398794/1500 Caldos 27 Ar 0-100% |
| ABB | AX410/50001 |
F 0 to 5g rms
*2 F 0 to 5mils pk-pk
G 0 to 10g rms
*2 G 0 to 10mils pk-pk
H 0 to 20g rms
*2 H 0 to 20mils pk-pk
Rectification
PATH A PATH B Recorder output Alarm reset
(DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
0 Average Value Average Value 0 4 to 20mADC 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET
1 pk-pk pk-pk 1 1 to 5VDC 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD
2 rms rms
2
Output card
/IS or /RE
option
A rms Average Value
B rms pk-pk
C Average Value rms
D pk-pk rms
(Code 2, A to D :
additional spec./RMS)
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
Alarm delay time
(DANGER)
Alarm delay time
(ALERT) Alarm output type First out*5
0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED
0 3 sec. 0 3 sec. 1 PATH A : 2 points (DANGER1,ALERT1)
PATH B : 2 points (DANGER2,ALERT2)
0 OFF
1 1 sec. 1 1 sec. 1 ON
1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED
2 6 sec. 2 6 sec.
2
PATH A : 4 points (DANGER1,DANGER2,
ALERT1,ALERT2)
PATH B : None
3 None 3 Non
rms. rectification Isolate output Recorder option
output
Input power supply
requirements*7 Tropical Sensitivity
correction
When rectification code 2, A to D is
selected, specify this option code.
0 4 to 20mADC 2 0 to -10VDC 0 85 to 264VAC 1 TIIS(IEC)
1 1 to 5VDC 3 0 to 10VDC 1 24VDC 7 NEPSI
2 0 to -10VDC 4 0 to -5VDC 2 110VDC 8 KTL
3 0 to 10VDC 5 0 to 5VDC
4 0 to -5VDC
5 0 to 5VDC
ALARM SET VALUE DANGER1 :
ALERT1 :
DANGER2 :
ALERT2 :
* DANGER1,ALERT1 : For PATH A
* DANGER2,ALERT2 : For PATH B
Unless specified otherwise, preset to :
DANGER : 100% of monitor range
ALERT : 90% of monitor range
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR. ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCDUCER
INPUT
CA Series, CV Series
Number of input points : 1 point
INPUT IMPEDANCE Approx.10k (CV-851 input)
Approx.50k (CV-852, CV-86, CV-87, CA input)
SEQUENCE SET
VALUE
(to increase alarm set
value during operation of
the sequence circuit)
: ×1.0 to 10.0 (×0.1 step)
Preset to ×1.0 unless specified otherwise.
CAUTION : Set the alarm set value so that its designated
multiple is within 110% of the measurement range
during operation of the sequence circuit.
If set to more than 110%, alarm may not be output.
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type:Dry contact
Contact for external reset
Contact for sequence
BAR GRAPH METER Recorder output conversion accuracy ±2.5% of F.S.
DIGITAL METER Recorder output conversion accuracy ±1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
±0.5% of F.S. at calibration frequency at 25°C
±2.0% of F.S. at calibration frequency at 0 to 65°C
(the calibration frequency is determined by the cut-off
frequency range.)
SUPPRESSION
FUNCTION SET VALUE
: 0.0 to 10.0 % of monitor range (0.1 % step)
Preset to 2.0 % unless specified otherwise.
CAUTION : When the measurement value is not more than
suppression function set value, indication and
recorder output value shall be as 0 %.
RECORDER OUTPUT
(FROM REAR PANEL) Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250)
4 to 20mADC (max.load resistance : 500)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100) (*option)
Number of output points : 2 points (PATH A, PATH B)
Standard Specifications
ALARM SET POINT 4 points(DA