Shinkawa

SHINKAWA MODEL VM-5C ECCENTRICITY MONITOR

MODEL VM-5C ECCENTRICITY MONITOR
onitor range
pk-pk
Monitor range
direct
Input signal
(Rotor pulse:CH1)
Input signal
(Ecc:CH2)
Direct
Eccentricity
polarity
*2
Measurement range
*3 Recorder
output
1 0 to 100 m pk-pk -50 to 0 to +50 m 1 VK-202A,VK-202P *1 1 VK-202A,VK-202P,FK-202F 1 Direct 1 1 to approx.300rpm 0 4 to 20mADC
2 0 to 200 m pk-pk -100 to 0 to +100 m 2 RD,FK Series 2 VK-302P,FK-302F 2 Reverse 2 1 to approx.600rpm 1 1 to 5VDC
3 0 to 250 m pk-pk -125 to 0 to +125 m 3 MS Series
4 or more pulses per
revolution with even duty
3 VK-452A,FK-452F
2
Output card
/IS or /RE
option
4 0 to 500 m pk-pk -250 to 0 to +250 m 4 VK-602P,FK-602F
5 0 to 1000 m pk-pk -500 to 0 to +500 m 5 VC Series(Voltage output only)
6 0 to 5mils pk-pk -2.5 to 0 to +2.5mils
7 0 to 10mils pk-pk -5 to 0 to +5mils
8 0 to 20mils pk-pk -10 to 0 to +10mils
A 0 to 30mils pk-pk -15 to 0 to +15mils
B 0 to 50mils pk-pk -25 to 0 to +25mils
Hysteresis set value
(shaped waveform circuit)
Alarm reset
(DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
First out
*4
Phase marker
input
0 1.0V 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET 0 NORMALLY
DE-ENERGIZED
0 NORMALLY
DE-ENERGIZED
0 NORMALLY
DE-ENERGIZED
0 OFF 0 CH1(VM-5C)
1 0.1V 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD 1 ON 1 CH1(VM-5P)
2 0.2V 1 NORMALLY
ENERGIZED
1 NORMALLY
ENERGIZED
1 NORMALLY
ENERGIZED

3 0.5V
Isolate output Recorder option
output
Input power supply
requirements*5
Tropical
spec.
Sensitivity
correction
0 4 to 20mADC 2 0 to -10VDC 0 85 to 264VAC 1 TIIS(IEC)
1 1 to 5VDC 3 0 to 10VDC 1 24VDC 2 FM
2 0 to -10VDC 4 0 to -5VDC 2 110VDC 4 CSA
3 0 to 10VDC 5 0 to 5VDC 5 ATEX
4 0 to -5VDC
5 0 to 5VDC

Ordering Information Standard Specifications
ALARM SET VALUE DANGER1 :
ALERT1 :
H-DANGER2 :
H-ALERT2 :
L-ALERT2 :
L-DANGER2 :
DANGER1,ALERT1 : For eccentricity pk-pk
DANGER2,ALERT2 : For direct
Unless specified otherwise, preset to :
DANGER1 : 100% of monitor range
ALERT1 : 90% of monitor range
H-DANGER2 : Invalid
H-ALERT2 : Invalid
L-ALERT2 : Invalid
L-DANGER2 : Invalid
MEASURED VALUE LCD digital meter with 5 digits (7 segments,with back light)
LCD bar graph meter (40 segments,with back light)
* Measurement value and alarm set value are indicated on the
digital meter and bar graph meter simultaneously.
ALAMR INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR. ALAMR
INDICATOR OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCER INPUT VK-202A,VK-202P,FK-202F,
VK-302P,FK-302F,VK-452A,FK-452F,VK-602P,FK-602F (only eccentricity),
VC Series(only eccentricity),
RD-05A(only phase marker),MS Series(only phase marker)
Number of input points : 2 points(phase marker,eccentricity)
NO. OF INPUT P/R Can be specified from 1 to 120 pulse.
Pulses/rev. :
INPUT IMPEDANCE Approx.50k
MIN. PULSE WIDTH Approx.50μsec
DIMENSION OF TARGET
(Model VK,RD,FK)
Note) To detect a projection (gear), provide surface A of the projection with a concentric curve.
Do not make it flat.
A= mm
B= mm
C= mm
D= mm

Foxboro FBM217
Foxboro FBM201 P0914SQ
Foxboro FBM237 P0914XS
Foxboro FBM203 RH914SV
Foxboro FBM201TA P0916AA
Foxboro FBM237TA P0916CC
Foxboro FBM203TA PO916AE
Foxboro P0916DE
ABB 3BHE057901R0101 PCD235C101
Triconex 3704E
Triconex 3504E
Triconex 3504E
EMERSON 1X00781H01L
EMERSON PR6423 009-041+CON 041/913-030
KONSGBERG RCU500

NO. OF INPUT PULSE 1 to 120 pulse
TRIGGER MODE AUTO, MANUAL (selectable)
In case of auto trigger mode, input pulse duty ratio should be between
10 and 90% and input pulse frequency should be 1Hz and over.
It depends on the target.
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type : Dry contact
Contact for external reset
BAR GRAPH METER Recorder output conversion accuracy  2.5% of F.S.
ZERO SHIFT 0 to 100% of monitor range
DIGITAL METER Recorder output conversion accuracy  1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
 1.0% of F.S. at 25°C
 2.0% of F.S. at 0 to 65°C
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250)
4 to 20mADC (max. load resistance : 500)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100) (*option)
Number of output points : 2 points(eccentricity pk-pk,direct)
SUPPRESSION
FUNCTION SET VALUE
: 0.0 to 10.0 % of monitor range (0.1 % step)
Preset to 2.0 % unless specified otherwise.
CAUTION : When the measurement value is not more than
suppression function set value, indication and
recorder output value shall be as 0 %.
MONITOR/PULSE
OUTPUT
(FROM FRONT,REAR
PANEL)
Monitor output/Pulse output, selectable
(preset to CH1 : Pulse output, CH2 : Monitor output)
Monitor output : Input signal is output via a buffer amplifier.
Signal level : -0.8 to -22VDC (VK,RD),± 15V (MS),
0 to 5VDC(VC)
Pulse output : Shaped pulse signal is output via a buffer
amplifier.
Signal level : -1 to +1V(PL),4 to 6V(PH)
Output impedance : Approx.100 (load resistance 50k or more)
Standard Specifications
ALARM SET POINT