Vibro-Meter PSU-VM600 VM600 Rack Power Module

PSU-VM600 VM600 Rack Power Module

Figures 6-1. 6-2 and 6-3 show block diagrams of the main different versions of the CPUM

card with their different CPU modules:

• Later versions of the CPUM card (PNR 200-595-076-HHh or later) fitted with

the PFM-541I or equivalent CPU module (see Figure6-1). This is an Ethernet redundant

version of the card.

• Later versions of the CPUM card (PNR 200-595-082-533 or later) fitted with

the PFM-541I or equivalent CPU module and the additional/redundant serial

communications module (see Figure6-2). This is a serial redundant version of the card.

• Earlier versions of the CPUM card (PNR 200-595-075-HHh or earlier) fitted with

the MSM586EN or equivalent CPU module (see Figure6-3). This is an Ethernet

redundant version of the card.

Similarly, Figure6-4 shows a block diagram of the IOCN card.

See 13Configuration of CPUM/IOCN cards for information on how to use the jumpers on

the CPUM and IOCN cards to modify the operation of the external communications

interfaces.

6.5 Serial port naming

For the CPUM card:

• The RS-232 serial port on the card’s panel, shown as RS-232 (COM0) in Figures 6-1.

6-2 and 6-3. corresponds to the RSFRONT device in the modbusDefault.cfg

configuration file.

(RSFRONT corresponds to the ser2 device driver of the QNX operating system used by

the CPUM card. This is the primary serial communications port.)

For the IOCN card:

• The serial port on the card’s panel, shown as RS (COM1) in Figure6-4. corresponds to

the RS device in the modbusDefault.cfg configuration file.

(RS corresponds to the ser3 device driver of the QNX operating system used by the

CPUM card. This is the secondary RS-serial communications port.)

• The serial ports on the card’s panel, shown as A (COM2) in Figure6-4. correspond to

the SERIAL_A device in the modbusDefault.cfg configuration file.

(SERIAL_A corresponds to the ser4 device driver of the QNX operating system used by

the CPUM card. This is the first of the additional serial communications ports and

requires that the optional additional/redundant serial communications module is fitted.)

• The serial ports on the card’s panel, shown as B (COM3) in Figure6-4. correspond to

the SERIAL_B device in the modbusDefault.cfg configuration file.

(SERIAL_B corresponds to the ser5 device driver of the QNX operating system used by

the CPUM card. This is the second of the additional serial communications ports and

requires that the optional additional/redundant serial communications module is fitted.)

Operation of LEDs on CPUM panel

6.6.1DIAG LED

The CPUM card’s DIAG LED is used for the following purposes:

• To indicate normal operation.

• To indicate the activation of special functions (related to CPUM security settings).

Further information is given in Table6-1.

Table6-1:Behaviour of DIAGLED

Behaviour of

DIAGLED Event(s)

Off (continuous) The CPUM is off or starting

Green (continuous)

The CPUM is operating normally and access to the CPUM card is

allowed (CPUM Access Lock: Unlocked).

That is, VM600 MPS rack (CPUM) security is not being used.

Green blinking slowly

(approximately once

per second)

The CPUM is operating normally but access to the CPUM card is

restricted (CPUM Access Lock: Locked).

That is, VM600 MPS rack (CPUM) security is being used.

Green blinking quickly

(approximately twice

per second) for five

seconds

The CPUM card is resetting to its default security settings.

That is, VM600 MPS rack (CPUM) security will not be used.

PROCESSING MODES AND APPLICATIONS

This chapter describes the processing modes that can be configured on the VM600 MPS (for

example, shaft relative vibration, broad-band pressure). Additional background information is

provided on the types of measurements that can be performed in these modes.

The MPS is generally fully configured in the factory before delivery and can be employed as

is. In some cases one of the VM600 MPSx software packages (MPS1 or MPS2) can be used

to allow further configuration of system parameters, or to reconfigure the MPS if it is extended

by the addition of MPC, IOC or relay cards (such as the RLC16).

NOTE: Refer to the relevant manual for further information: VM600 MPS1 software

manual or VM600 MPS2 software manual.

7.1 Different versions of the MPC4 card

The MPC4 machinery protection card is available in different versions, including a standard

version, a separate circuits version and a safety (SIL) version, as described in

4MPC4/ IOC4T card pair.

However, the safety MPC4 card (that is, the MPC4SIL) does not provide all of the signal

processing capabilities supported by the standard and the separate circuits versions of the

MPC4 (seeTable7-1)