Vibro-Meter ABE056 – 1U ultra-thin single-rack
ABE056 – 1U ultra-thin single-rack
Different versions of the CPUM card
In 2015. the CPUM card was updated to use a new PC/104 CPU module (PFM-541I or
equivalent) that supports two Ethernet interfaces by default, which required updates to the
underlying carrier board (that is, the CPUM card itself).
Previously, the CPUM card was fitted with a CPU module (MSM586SEN or equivalent) that
supported one Ethernet interface by default and required an additional Ethernet controller
module (MSME104 or equivalent) to be fitted in order to be Ethernet redundant.
So the different versions of the CPUM card in use are:
• Later versions of the CPUM card (PNR 200-595-076-HHh or later) fitted with
the PFM-541I or equivalent CPU module (see Figure6-1).
• Earlier versions of the CPUM card (PNR 200-595-075-HHh or earlier) fitted with
the MSM586EN or equivalent CPU module (see Figure6-3).
NOTE: Due to changes to the underlying CPUM card (carrier board), the later versions of
the CPUM card are not compatible with the earlier versions of the CPUM card.
Accordingly, the PFM-541I or equivalent CPU module can only be used with the
later versions of the CPUM card (PNR 200-595-076-HHh or later) and the
MSM586EN or equivalent CPU module can only be used with the earlier versions
of the CPUM card (PNR 200-595-075-HHh or earlier).
6.2General overview
The CPUM card is a modular CPU (central processing unit) card that acts as “rack controller”
in a networked VM600 system. Depending on system requirements, the CPUM can be used
either alone in the rack (installed in the front card cage) or in conjunction with the associated
IOCN input/output card (installed in slot0 of the rear card cage, directly behind the CPUM).
The CPUM card consists of a carrier board with two PC/104 type slots that can accept
different PC/104 modules, typically a CPU module in PC/104 slot1 and an optional serial
communications module in PC/104 slot2.
All CPUM cards are fitted with a CPU module (PC/104 slot1) that supports two Ethernet
connections (primary and secondary) and two serial connections (primary and secondary).
That is, both the Ethernet redundant (PNR200-595-0Ss-33h) and serial redundant
(PNR200-595-0Ss-53h) versions of the CPUM card.
The CPUM card with the CPU module provides:
• Primary Ethernet communications via the ‘NET’ connector (8P8C (RJ45)) on the CPUM
card’s panel or the ‘1’ connector (8P8C (RJ45)) on the IOCN card’s panel, if used.
NOTE: The ‘NET’ connector on the CPUM card and the ‘1’ connector on the IOCN
card are mutually exclusive, that is, only one can be used at any one time
(configured using jumpers on the CPUM).
• Secondary Ethernet communications via the ‘2’ connector (8P8C (RJ45)) on the IOCN
card’s panel, if used.
• Primary RS-232 communications via the ‘RS232’ connector (D-sub (DE-09)) on the
CPUM card’s panel.
• Secondary RS-232 or RS-485 communications via the ‘RS’ connector (6P6C
(RJ12/RJ25)) on the IOCN card’s panel, if used
The CPUM card can also be fitted with an optional serial communications module (PC/104
slot2) in order to support additional/redundant serial connections. This is, the serial
redundant version of the card (PNR200-595-0Ss-53h).
The CPUM card with the additional/redundant serial communications module provides:
• RS-485 (115.2kbps) communications as either half-duplex (2-wire) or
full-duplex(4-wire) via the ‘A’ and ‘B’ connectors (6P6C (RJ12/RJ25)) on the IOCN
card’s panel.
NOTE: The additional ‘A’ and ‘B’ serial connections can be used to configure multi-drop
RS-485 networks of VM600 racks using ModbusRTU communications.
A diagnostic LED (named DIAG) on the panel of the CPUM indicates the CPUM card status,
such as normal operation and whether VM600 MPS rack (CPUM) security is being used. The
CPUM card’s panel also contains an LCD display for showing the level of a selected
monitored output in bar-graph and digital form. The Alert and Danger levels are also indicated
on the bar graph.
Coloured LEDs (named OK, A and D) on the panel of the CPUM indicate the OK, Alert and
Danger status for the signal selected for display (see Figure2-12). If slot0 is selected, these
LEDs will indicate the general rack status.
SLOT and OUT (output) keys on the panel are used to select which signal to display. The
ALARM RESET button on the panel resets all latched alarms (and associated relays) for the
entire rack.
Possibilities allowed by the CPUM/ IOCN pair include:
• ‘One-shot’ configuration of all VM600 cards using a direct Ethernet or RS-232 serial
connection from an external computer (laptop, notebook, pen-computer, industrial
computer or flat-panel computer) running the VM600 MPSx software (MPS1 or MPS2),
from the Meggitt vibro-meter® product line.
• ‘One-shot’ configuration of all VM600 cards via Ethernet from a networked computer
running the VM600 MPSx software.
• Visualisation of signal levels and alarm limits using the display on the CPUM card’s
panel.
• External communication with third party devices such as a DCS or PLC.
| ABB | IMASI02 |
| ABB | IMASI03 |
| ALSTOM | V4559828-0001 |
| GE | P111-6052 |
| ABB | 540CMD01 |
| GE | IS220PSVOH1A |
| GE | IS220PDIOH1A |
| GE | IS200BAPAH1A |
| EMERSON | 5X00419G02 |
| ABB | 3AUA0000110430 BCU-12 |
| BENDER | IRDH275B435 |
| GE | IS230PCAAH1B |
| GE | IS220PAICH1B |
| GE | IS220YDOAS1A |
| GEA | 0005-4050-430 |
| Rolls-royce | R10I53S-MRP1TR01.5 |
| Hirschmann | RS20-0800M4M4SDBEHH |
| Hirschmann | RS30-0802OOZZSDAEHH |
| Hirschmann | MS20-1600SABEHH |
| Hirschmann | MM20-T1T1T1T1SBHH |
| Hirschmann | MM20-Z6Z6Z6Z6SBHH |
| TRICONEX | 3721 |
| TRICONEX | 3009 |
| TRICONEX | 3009X |