Alarm Types

Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)

Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.

Note:In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.

To use alarm 1, set the output assignment to alarm 1.

Set

value Alarm type

Alarm output operation

Description of function When alarm value X

is positive

When alarm value X

is negative

0 Alarm function OFF Output OFF No alarm

1 Upper- and lower-limit *1 *2

Set the upward deviation in the set point for the alarm upper

limit (H) and the lower deviation in the set point for the alarm

lower limit (L). The alarm is ON when the PV is outside this

deviation range.

2

(default) Upper-limit

Set the upward deviation in the set point by setting the alarm

value (X). The alarm is ON when the PV is higher than the

SP by the deviation or more.

3 Lower-limit

Set the downward deviation in the set point by setting the

alarm value (X). The alarm is ON when the PV is lower than

the SP by the deviation or more.

4 Upper- and lower-limit

range *1 *3

Set the upward deviation in the set point for the alarm upper

limit (H) and the lower deviation in the set point for the alarm

lower limit (L). The alarm is ON when the PV is inside this

deviation range.

5 Upper- and lower-limit with

standby sequence *1 *4 A standby sequence is added to the upper- and lower-limit

alarm (1). *6

6 Upper-limit with standby

sequence A standby sequence is added to the upper-limit alarm (2). *6

7 Lower-limit with standby

sequence A standby sequence is added to the lower-limit alarm (3). *6

8 Absolute-value upper

limit

B7AM-8B16

The alarm will turn ON if the process value is larger than the

alarm value (X) regardless of the set point.

9 Absolute-value lower-limit The alarm will turn ON if the process value is smaller than the

alarm value (X) regardless of the set point.

10​

Absolute-value upper

limit with standby

sequence

A standby sequence is added to the absolute-value upper

limit alarm (8). *6

11 Absolute-value lower-limit

with standby sequence

A standby sequence is added to the absolute-value lower

limit alarm (9). *6

12 LBA (alarm 1 type only)-*7

13 PV change rate alarm-*8

14 SP absolute-value

upper-limit alarm

This alarm type turns ON the alarm when the set point (SP)

is higher than the alarm value (X).

15 SP absolute-value

lower-limit alarm

This alarm type turns ON the alarm when the set point (SP)

is lower than the alarm value (X).

16 MV absolute-value

upper-limit alarm *9

Standard Control Standard Control

This alarm type turns ON the alarm when the manipulated

variable (MV) is higher than the alarm value (X). Heating/Cooling

Control (Heating MV)

Heating/Cooling

Control (Heating MV)

Always ON

17 MV absolute-value

lower-limit alarm *9

Standard Control Standard Control

This alarm type turns ON the alarm when the manipulated

variable (MV) is lower than the alarm value (X). Heating/Cooling

Control (Cooling MV) Heating/Cooling

Control (Cooling MV)

Always ON

18 RSP absolute-value

upper-limit alarm *10

This alarm type turns ON the alarm when the remote SP

(RSP) is higher than the alarm value (X).

19 RSP absolute-value

lower-limit alarm *10

This alarm type turns ON the alarm when the remote SP

(RSP) is lower than the alarm value (X)

KS1-15*B Yokogawa   AKB331 Signal Cable (50-50 pins)
TC-OAH061 Honeywell Analog Output Module
HMD01.1N-W0020-A-07-NNNN REXROTH HMV   series power supply device
MPS015 13100205 Power Supply SCHROFF
3BSC690076R5 SCHROFF VME-RACK
HAO805 Symphony Plus SD Series HART I/O   ABB
MVME51105E-2161 VMEbus Single-Board   Computer MOTOROLA
DLQW72-PC-PY DEIF Bridge wing indicator
BG65X50SI Dunkermotoren continuous   current dynamo
VTR-5-PY DEIF Bridge wing indicator
MVI94-MCM-MHI ProSoft Modbus Mitsubishi   Heavy Industries Network Interface Module
DPS112 Kongsberg MARITIME DGNSS SENSOR   FOR WORLDWIDE OPERATIONS
IRDH275B-435BENDER Digital Ground Fault   Monitor / Ground Detector
TK-CCR014 Honeywell C200E Control   Processor
FC-SDO-0824V1.3 HONEYWELL Safe Digital   Output FTA
UNITROL 1020-0003 BASIC 3BHE030579R0003   Indirect excitation system ABB
UNITROL 1020-0004 BASIC+SYNC   3BHE030579R0004 FULL 3BHE030579R0006 Indirect excitation system ABB
UNITROL 1020-0006 FULL 3BHE030579R0006   Indirect excitation system ABB
UNITROL 1020-0007FULL+PSS   3BHE030579R0007 Indirect excitation system ABB
CMA130 3DDE300410 Controller panel ABB
SQ-300I 8700700-006 Hybrid automatic   voltage control (AVC) B&W
YT204001-BT ABB Modem Board YPC104B
2098-DSD-020X/B Ultra 3000 Digital Servo   Drive Allen Bradley
8273-1402301D Woodward Load Sharing and   Speed Controls
PCI-6230 NI Multifunction DAQ

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注