Woodward easYgen-2500-5/P1 8440-1884
Woodward easYgen-2500-5/P1 8440-1884
A generator system that is connected to the load through a 3
phase, 4-wire connection but have the device wired for a 3-phase,
3-wire installation may have the L2 phase grounded on the secon
dary side. In this application the device will be configured for 3
phase, 4-wire OD for correct power measurement.
Power Factor is defined as a ratio of the real power to apparent
power. In a purely resistive circuit, the voltage and current wave
forms are instep resulting in a ratio or power factor of 1.00 (often
referred to as unity).
In an inductive circuit the current lags behind the voltage waveform
resulting in usable power (real power) and unusable power (reac
tive power). This results in a positive ratio or lagging power factor
(i.e. 0.85lagging).
In a capacitive circuit the current waveform leads the voltage wave
form resulting in usable power (real power) and unusable power
(reactive power). This results in a negative ratio or a leading power
factor (i.e. 0.85leading)
Inductive Capacitive
Load type Electrical load whose current waveform lags the
voltage waveform thus having a lagging power
factor. Some inductive loads such as electric motors
have a large startup current requirement resulting in
lagging power factors.
Electrical load whose current waveform leads the
voltage waveform thus having a leading power
factor. Some capacitive loads such as capacitor
banks or buried cable result in leading power fac
tors.
Different power factor
display on the unit
i0.91 (inductive)
lg.91 (lagging)
c0.93 (capacitive)
ld.93 (leading)
Reactive power display
on the unit
70 kvar (positive)-60 kvar (negative)
Output of the interface + (positive)- (negative)
Current relation to
voltage
Lagging Leading
Generator state Overexcited Underexcited
Control signal If the control unit is equipped with a power factor controller while in parallel with the utility:
A voltage lower “-” signal is output as long as the
measured value is “more inductive” than the refer
ence setpoint
Example: measured = i0.91; setpoint = i0.95
A voltage raise “+” signal is output as long as the
measured value is “more capacitive” than the refer
ence setpoint
Example: measured = c0.91; setpoint = c0.95
Discrete inputs may be configured to normally open (N.O.) or nor
mally closed (N.C.) states.
Fig. 57: Discrete inputs – state N.O.
In the state N.O., no potential is present during normal operation; if
an alarm is issued or control operation is performed, the input is
energized.
Fig. 58: Discrete inputs – state N.C.
In the state N.C., a potential is continuously present during normal
operation; if an alarm is issued or control operation is performed,
the input is de-energized
The N.O. or N.C. contacts may be connected to the signal terminal
as well as to the ground terminal of the discrete input ( Ä “Sche
matic and terminal assignment” on page 73).
It is recommended to use two-pole analog senders. This ensures
an accuracy of ≤ 1 % for 0 to 500 Ohm inputs and ≤ 1.2 % for 0 to
20 mA inputs.
The following senders may be used for the analog inputs:
n 0 to 20 mA
n Resistive (0 to 500 Ohm)
n VDO, 0 to 180 Ohm; 0 to 5 bar, Index “III”; 0 to 10 bar, Index
“IV”
n VDO, 0 to 380 Ohm; 40 to 120°, Index “92-027-004; 50 to 125°,
Index “92-027-006
| ABB | 3HAC17346-1/01 |
| ABB | 086348-001 |
| ABB | YPP110A |
| ABB | 086329-004 |
| ABB | 086370-001 |
| ABB | UFC762AE101 3BHE006412R0101 |
| ABB | SPNPM22 |
| ABB | TPPB-02 |
| ABB | TU830V1 3BSE013234R1 |
| ABB | SPBRC410 |
| ABB | CDP312R |
| ABB | 086339-001 |
| ABB | 1TGE120021R0010 |
| ABB | LXN1604-6 |
| ABB | PPC905AE101 3BHE014070R0101 |
| ABB | HIEE300024R4 UAA326A04 |
| ABB | PM511V16 3BSE011181R1 |
| ABB | GOP2 |
| ABB | 5SHY4045L0006 3BHB030310R0001 |
| ABB | 086444-005 |
| ABB | UFC911B106 3BHE037864R0106 |
| ABB | UFC921A101 3BHE024855R0101 |