ALSTOM

ALSTOM  PIB314C Power Interface / Measurement Board

PIB314C Power Interface / Measurement Board

Introduction to the use of the second CAN port

Current models of the ALSPA MV3000e provide the Extended

I/O, CANopen and DeviceNet protocols from the CAN port

provided on the CDC control board.

The latest models of ALSPA MV3000e drives can support a

second CAN port, offering all the facilities provided on the CDC

CAN port.

This manual describes the installation and use of second CAN

port with the later models of drives that are able to support it.

This manual assumes that the user has access to the CANopen

and DeviceNet manuals listed below.  These manuals provide a

detailed description of the CAN menu parameters and an

overview of the protocols provided, together with set up

examples.

T2013

T2017

2. Specification

The second CAN port supports the CANopen, Extended I/O and

DeviceNet protocols as described in the ALSPA MV3000e

CANopen user manual and the ALSPA MV3000e DeviceNet

user manual.

This software facility is incorporated as standard in drives fitted

with Version 9.00 or later:

CDC required: 20X4311 issue E or later

OR      20X4341 issue C or later

The following sub-sections supersede the equivalent sub

sections found in the above manuals.

2.1.1

Supported Baud Rates

In common with the primary CAN port on the CAN 2 capable

CDCs, the second CAN port can be configured to communicate

at the standard CANopen rates between 20 k Baud and 1M

Baud.

The Baud rate selection is from the following list:

• 20 k Baud

• 50 k Baud

• 100 k Baud

• 125 k Baud

• 250 k Baud

• 500 k Baud.

• 1M Baud

DeviceNet is limited to a subset of the above Baud rates, i.e.

• 125 k Baud

• 250 k Baud

• 500 k Baud

Opto-Isolation

ALSPA MV3000e 2nd CAN Port

In common with the primary CAN port on the CAN 2 capable

CDCs, full opto-isolation is provided.  The opto-isolated CAN

transceiver is powered by an on-board DC to DC converter.

There is no requirement to provide CAN-side external power.

2.2 Connector Specification

2.2.1

Connectors and Connections

The CANbus connection is achieved via the CAN_HI and

CAN_LO and COMMS_GND terminals provided on Terminal

Block TB7/TB7B as detailed in Table 4-1.

The connections at TB7/TB7B are made by screw-type

terminations for each separate flexible cable.

All cables should have strain relief to prevent damage to the

CANbus connection at TB7/TB7B.