ALSTOM

ALSTOM IC687BEM744 Bus Controller

2.3. Assigning IP address

The IP address is used to identify each controller on the Ethernet network.

Therefore, each controller on the network must have a unique IP address.

2.3.1. The Ethernet board location

To manually assign an IP address to a controller its Ethernet boards dip

switches are used. The location of the Ethernet board differs depending on

product, see figure 2 below.

Ethernet LEDs

12345678

ON

ON

EFFIC Controller

Figure 2. The Ethernet board location

The Ethernet board has four LEDs carrying the following information:

LED Colour LED status Legend

Green

Green

Green

Cont.

Not lit

1 Hz

The module has a link

The module does not sense a link

IP address not set by using the DIP-switch

2 Red 1 H

12345678

ON

z Invalid MAC address (internal error)

2 Red 2H

z Failed to load Ethernet configuration from

FLASH memory

2 Red 4 H

z Internal error

Red

Green

Green

Cont.

Duplicate IP addresses detected

Blinking N/A

Blinking Blinks each time a package is received or

transmitted.

Assigning the IP address to the controller

There are many different ways to assign ip addresses, in this manual the

three most common will be described in the three following sections.

The Ethernet board has a default IP address setting of:

IP address:192.168.0.X

The X in the IP address can be set from 1 to 255 by the configuration switch

on the ethernet board. The switch represents the binary value of the X value

in the IP address.

Example:

The switches are set to

00010100 (20 decimal).

The IP address will be set

to 192.168.0.20

2.3.4. Using configuration switch

ON

12345678

MSB

Make sure that the controller is switched Off.

LSB

Use the configuration switch to assign a unique ip number to the con

troller, a number not used by any other nodes in the network.

Switch On the controller.

Repeat step 1-3 with all the controllers in the network.

Now the IP address of the PC has to be set (the PC that is used for

running the PC MTU software and browsing the web pages).

Note, Assigning IP address to the computer may differ

depending on operating system.

On the PC – click the START button and select Control Panel.

In Control Panel select Network and Dial-up connections and then

Local Area Connection.

Select Properties and highlight Internet Protocol (TCP/IP) and select

Properties.

Click the radio button Specify an IP Address.

10. In the IP address field assign a unique ip number not used by any other

nodes in the network to the PC e.g. 192.168.0.100. The Subnet mask

will normally be automatically filled in (255.255.255.0).

Click OK and close all windows.

11. To complete the setup start the PC-MTU program.

12. From the menu Choose Advanced > Ip config.